Contents Start Up Getting Other Information and Publications General .............. 15 Topping Off System Charge ........15 Wall Mount General Information Safety Practices ............. 15 Wall Mount Model Nomenclature ......4 Important Installer Note ......... 16 Shipping Damage ............ 4 Wall Mounted Air Conditioner ........
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE – CONTROL MODULES REVISIONS MODEL NUMBER (See Spec. Sheet S3397) CAPACITY 18 - 1½ Ton VOLTS & PHASE COIL OPTIONS 24 - 2 Ton A - 230/208/60/1 X - Standard COLOR OPTIONS 30 - 2½...
Any grille that meets with 5/8 inch louver criteria may be top of the unit down to the unit base. There are used. It is recommended that Bard Return Air Grille Kit openings in the unit base for the drain hose to pass RG2 through RG5 or RFG2 through RFG5 be installed through.
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings WARNING must be cut through the wall as shown in Figure 3. 2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the Failure to provide the 1/4 inch clearance unit without transmitting any unit vibration.
FIGURE 2 All dimensions are in inches. Dimensional drawings are not to scale. W**H RIGHT UNIT BACK VIEW SIDE VIEW FRONT VIEW *Optional top outlet (factory installed only) for W30H and W36H models only. Manual 2100-511 Page 7 of 27...
FIGURE 4 ELECTRIC HEAT CLEARANCE W30H1, W36H1, W42H1, W48H1, W60H1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting.
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED Manual 2100-511 Page 12 of 27...
WIRING – LOW VOLTAGE WIRING WIRING – MAIN POWER 230/208V, 1 phase and 3 phase equipment dual primary Refer to the unit rating plate for wire sizing information voltage transformers. All equipment leaves the factory and maximum fuse or “HACR” type circuit breaker wired on 240V tap.
7. Never fill cylinders over 80% of total capacity. TOPPING OFF SYSTEM CHARGE 8. Store cylinders in a cool area, out of direct If a leak has occurred in the system, Bard Manufacturing sunlight. recommends reclaiming, evacuating (see criteria above), 9.
START UP (Continued) IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil All units with three phase scroll compressors are with a dish washing detergent. equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH &...
If some abnormal or temporary condition such as a high SEQUENCE OF OPERATION wind causes the heat pump to have a prolonged defrost Circuit R-Y makes at thermostat pulling in COOLING – cycle, the heat pump control will restore the system to compressor contactor, starting the compressor and heating operation automatically after 10 minutes.
TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL 4. Set system switch to “heat” or “cool”. Adjust TROUBLESHOOTING PROCEDURE thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start. 1. NOTE: A thorough understanding of the defrost NOTE: If there was no power to 24 volt transformer, cycle sequence is essential.
CHECKING TEMPERATURE SENSOR 3. Check resistance reading to chart of resistance. Use OUTSIDE UNIT CIRCUIT sensor ambient temperature. (Tolerance of part is ± 10%.) 1. Disconnect temperature sensor from board and from outdoor coil. 4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the 2.
TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS REFRIGERANT CHARGE Shown in Figure 9 is the correct fan blade setting for The correct system R-410A charge is shown on the unit proper air delivery across the outdoor coil. Refer to rating plate. Optimum unit performance will occur with Table 2 for unit specific dimension.
TABLE 4A COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Low side pressure ± 4 PSIG High side pressure ± 10 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate charge weight.
TABLE 5 Electrical Specifications — W**H Series s t l 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity”...