CONTENTS Getting Other Information and Publications Start Up ..............15 General ............15 Wall Mount General Information ......4 Topping Off System Charge ......... 15 Wall Mount Model Nomenclature ......4 Safety Practices ..........15 Shipping Damage ..........4 Important Installer Note ........16 General ..............
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help when installing the For more information, contact these publishers: furnace. They can usually be found at the local library or purchased directly from the publisher. Be sure to ACCA Air Conditioning Contractors of America consult the current edition of each standard.
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE – CONTROL MODULES REVISIONS MODEL NUMBER (See Spec. Sheet S3398) CAPACITY 18 - 1½ Ton COIL OPTIONS VOLTS & PHASE H - Heat Pump 24 - 2 Ton A - 230/208/60/1 COLOR OPTIONS X - Standard 30 - 2½...
Any grille that meets with 5/8" louver criteria may be a drain system of some type, it must be an open or used. It is recommended that Bard Return Air Grille vented type system to assure proper drainage. Kit RG-2W through RG-5W or RFG-2W through RFG- 5W be installed when no return duct is used.
INSTALLATION WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. 2. On wood frame walls, the wall construction must Failure to provide the 1/4" clearance between be strong and rigid enough to carry the weight of the supply duct and a combustible surface the unit without transmitting any unit vibration.
FIGURE 4 Electric Heat Clearance W30H2, W36H2, W42H2, W48H2, W60H2 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3ʹ...
FIGURE 5 Wall Mounting Instructions WALL STRUCTURE SEE FIGURE 3 – MOUNTING INSTRUCTIONS FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
FIGURE 7 Common Wall Mounting Installations SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
WIRING – LOW VOLTAGE WIRING WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information All 230/208V 1 phase and 3 phase equipment have All equipment and maximum fuse or circuit breaker size. Each dual primary voltage transformers. outdoor unit is marked with a “Minimum Circuit leaves the factory wired on 240V tap.
7. Never fill cylinders over 80% of total capacity. TOPPING OFF SYSTEM CHARGE 8. Store cylinders in a cool area, out of direct If a leak has occurred in the system, Bard sunlight. Manufacturing recommends reclaiming, evacuating 9. Never heat cylinders above 125°F.
IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance, wash the indoor All units with three phase scroll compressors are coil with a dishwashing detergent. equipped with a three phase line monitor to prevent compressor damage due to phase reversal. HIGH AND LOW PRESSURE SWITCH The phase monitor in this unit is equipped with two LEDs.
SEQUENCE OF OPERATION When the temperature rises to approximately 57°F, the coil temperature sensor will send a signal to the heat COOLING – Circuit R-Y makes at thermostat pulling pump control which will return the system to heating in compressor contactor, starting the compressor operations automatically.
Pressure will rise fairly fast as there is likely no actual After this period expires, the control will then monitor frost on the outdoor coil in this artificial test condition. the low pressure switch input normally to make sure that the switch is closed during “Y” operation. There is also a 5-minute compressor time delay function built into the HPC.
SERVICE SOLID STATE HEAT PUMP CONTROL 4. Set system switch to “heat” or “cool”. Adjust TROUBLESHOOTING PROCEDURE thermostat to call for heat or cool. The indoor blower, compressor and outdoor fan should start. 1. NOTE: A thorough understanding of the defrost cycle sequence is essential.
CHECKING TEMPERATURE SENSOR 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of OUTSIDE UNIT CIRCUIT part is ± 10%.) 1. Disconnect temperature sensor from board and 4. If sensor resistance reads very low, then sensor is from outdoor coil.
FAN BLADE SETTING DIMENSIONS REMOVAL OF FAN SHROUD The correct fan blade setting for proper air delivery 1. Disconnect all power to the unit. across the outdoor coil is shown in Figure 9. Refer to 2. Remove the screws holding both grilles, one on Table 2 for unit specific dimension.
TABLE 3A – Cooling Pressure Table RETURN AIR TEMPERATURE ENTERING OUTDOOR COIL MODEL PRESSURE 75° 80° 85° 90° 95° 100° 105° 110° 115° 120° TEMP. 75 DB Low Side 62 WB High Side 80 DB Low Side W18H2 67 WB High Side 85 DB Low Side...
TABLE 4A Electrical Specifications Single Circuit Dual Circuit Minimum Maximum Rated Volts Field Maximum Field Circuit External Fuse or Field Power Ground MODEL Minimum & Phase Power External Power Ground Ampacity Ckt. Breaker Wire Size Wire Size Circuit Circuits Fuse or...
TABLE 4B Electrical Specifications — Dehumidification Models Single Circuit Dual Circuit Minimum Maximum Rated Volts Field Maximum Field Circuit External Fuse or Field Power Ground MODEL Minimum & Phase Power External Power Ground Ampacity Ckt.
TABLES 7 Maximum ESP of Operation Electric Heat Only Model Front Outlet Top Outlet Model High High W18H Speed Speed Speed Speed W24H W30H W24H W36H W24H W30H W36H W30H W36H W42H W48H W60H Model Speed KW High Speed Low Speed High Speed Low Speed High Speed...