CONTENTS Getting Other Information and Publications ..3 Service ..............25 Wall Mount General Information ......4 Solid State Heat Pump Control Troubleshooting Heat Pump Wall Mount Model Nomenclature ..4 Procedure ............25 Shipping Damage ..........4 Checking Temperature Sensor Outside General ...............
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE – CONTROL MODULES REVISIONS MODEL NUMBER (See Spec. Sheet S3585) CAPACITY 18 - 1½ Ton VOLTS & PHASE COIL OPTIONS H - Heat Pump 24 - 2 Ton A - 230/208/60/1 X - Standard COLOR &...
Any grille that meets with 5/8" louver criteria may be in place and is recommended for maximum energy efficiency. used. It is recommended that Bard Return Air Grille Kit RG-2W through RG-5W or RFG-2W through RFG- The blank-off plate is available upon request from the 5W be installed when no return duct is used.
INSTALLATION Basic Installation Design and contact with the base of the unit. If allowed, this could cause damage to the coil and other Application Planning base components. Also, be sure there are no Successful unit installations require proper planning air obstructions to the sides or front of the and site inspection before installation begins.
5/8". It is recommended that a Maximum External Static Pressure (ESP) of Operation Bard Return Air Grille Kit be installed that is designed Table 17 on page 36. Design the duct work according specifically for the wall mount product. Contact the to methods given by the Air Conditioning Contractors local Bard distributor or visit www.bardhvac.com for...
Unit Installation flashing is supplied for field use and is mounted to the back of the unit for shipping. Remove rain Make sure to have the proper tools at the work site that flashing before locating the unit against wall. Top are needed for unit installation.
2. Field ventilation installation with the unit installed requires 40" on the left or right side of the unit. 3. Bard recommends a minimum of 10' between the unit front condenser air outlet and solid objects including fences, walls, bushes and other airflow obstructions.
FIGURE 4 Electric Heat Clearance W30H and W36H SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL-MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES. WARNING Fire hazard. Maintain minimum 1/4" clearance between the supply air duct and combustible materials in the first 3' of ducting.
FIGURE 5 Wall Mounting Instructions WALL STRUCTURE SEE FIGURES 3A-B – MOUNTING INSTRUCTIONS FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR SUPPLY AIR SUPPLY AIR DUCT OPENING OPENING RETURN AIR RETURN AIR RETURN AIR OPENING OPENING OPENING BOTTOM MOUNTING WOOD OR STEEL SIDING BRACKET.
FIGURE 7 Common Wall Mounting Installations SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN RAIN FLASHING RAFTERS FLASHING RAFTERS FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT FINISHED CEILING SURFACE W/ GRILLE RETURN AIR RETURN AIR OPENING W/ GRILLE...
Wiring – Main Power Low Voltage Connections These units use a 24-volt AC low voltage circuit. Refer to the unit rating plate for wire sizing information and maximum fuse or circuit breaker size. Each C terminal is 24VAC common and is grounded. outdoor unit is marked with a “Minimum Circuit G terminal is the indoor blower input.
TABLE 3 Units with an economizer will not have the brass jumper installed. Refer to vent manuals for instructions on how Low Voltage Connections Balanced Climate works with each vent. Units w/ To operate in Balanced Climate mode, a 2-stage cooling Standard Units Economizers thermostat is required.
TABLE 4 Wall Thermostats Part Number Predominate Features 8403-057 1 stage Cool, 1 stage Heat; Electronic Non-Programmable; Auto or Manual changeover (TH3110D1040) 8403-059 2 stage Cool, 2 stage Heat; Electronic Non-Programmable; HP or Conventional (Default: AC); Auto or Manual (TH5220D1219/U) changeover 8403-060 3 stage Cool;...
Page 18
Programmable Thermostat Connections Completestat Model #CS9B-THO or Model #CS9BE-THO W1/E Thermostat W1/E YO/D Bard #8403-060 Optional CO2 Controller Bard Part #8403-067 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
(TH311OD1040) or T4 Pro 8403-089 8403-058 (TH522OD1151) 8403-047 8403-059 (TH522OD1219/U) Electronic Humidistat or T6 Pro 8403-090 Optional CO2 Controller Bard Part #8403-067 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
Topping Off System Charge 10. Never trap liquid R-410A in manifold sets, gauge lines or cylinders. R-410A expands significantly If a leak has occurred in the system, Bard at warmer temperatures. Once a cylinder or line is Manufacturing recommends reclaiming, evacuating...
The phase monitor in this unit is equipped with two If the Bard air conditioning system is being set up LEDs. If the Y signal is present at the phase monitor in a typical environment where 72°F is the lowest and phases are correct, the green LED will light.
1/4" QC, to short between the SPEEDUP If the unit is being installed with any ventilation terminals to accelerate the HPC timer and initiate package, a Bard LAC kit must be installed. Failure to defrost. utilize an LAC with any air conditioner can cause coil Be careful not to touch any other terminals with the freeze up.
Service Hints After this period expires, the control will then monitor the low pressure switch input normally to make sure 1. Caution owner/operator to maintain clean air that the switch is closed during “Y” operation. filters at all times and to not needlessly close off High Pressure Switch Operation supply and return air registers.
SERVICE Solid State Heat Pump Control NOTE: If there was no power to 24 volt transformer, Troubleshooting Procedure the compressor and outdoor fan motor will not start for 5 minutes. This is because of the 1. NOTE: A thorough understanding of the defrost compressor short cycle protection.
Checking Temperature Sensor Outside 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part Unit Circuit is ± 10%.) 1. Disconnect temperature sensor from board and 4. If sensor resistance reads very low, sensor is from outdoor coil.
“Continuous Fan” only problem identified. on the “G” terminal. NOTE: Bard Models PA13242; PA13302; PA13362-A, -B; PA13422-A, -B, -C; PA13482-A, -B, -C; PA13602-A, -B, -C 2. If the system is excessively noisy, does not appear contain the X13-Series Motors.
TROUBLESHOOTING GE X13-SERIES ECM2.3 ™ MOTORS CONT’D. Model SelecTech Communication Diagnostics B. If the motor has proper high voltage as identified above (If the Motor Is Not Running 2. Initiate a demand from the thermostat and check the The SelecTech motor is communicated through 24 VAC Model X13 Communication Diagnostics #1 on page 27), proper low voltage to a voltage between the common and the appropriate motor...
Fan Blade Setting Dimensions Removal of Fan Shroud The correct fan blade setting for proper air delivery 1. Disconnect all power to the unit. across the outdoor coil is shown in Figure 13. Refer to 2. Remove the screws holding both grilles, one on Table 10 for unit specific dimension.
TABLE 11A Cooling Pressure Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W18HB 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W24HB 80/67 High Side Low Side...
TABLE 12 Cooling Pressure – Balanced Climate Airflow Air Temperature Entering Outdoor Coil °F Return Air Temp Model Pressure (DB/WB) Low Side 75/62 High Side Low Side W18HB 80/67 High Side Low Side 85/72 High Side Low Side 75/62 High Side Low Side W24HB 80/67...
TABLE 13 Electrical Specifications Single Circuit Dual Circuit Minimum Maximum Rated Volts Field Maximum Field Circuit External Fuse Field Power Ground Model Minimum & Phase Power External Power Ground Ampacity or Ckt. Breaker Wire Size Wire Size Circuit Circuits Fuse or...
24VAC signals from the low voltage terminal block located inside the control panel by a thermostat or other controlling device. Each speed tap is programmed by Bard at the factory to different motor torque settings (see Figure 14). Manual...
Speed Tap 1 – Vent/Blower Only the jumper between Y1 and Y2 installed and it must be removed to use Balanced Climate mode. The unit Speed taps 1 and 3 are programmed to identical is shipped with the orange/black wire connected to torque settings in the ECM motor.
TABLE 17 Maximum ESP of Operation Electric Heat Only Model Front Outlet Model A00/0Z High W18H Speed Speed W24H A00/0Z B00/0Z W30H W24H W36H C00/0Z W24H B00/0Z W30H W36H C00/0Z W30H W36H TABLE 18 Electric Heat Models 240V-1 208V-1 240V-3 208V-3 460V-3 Amps...