TREND IQECO31/230 Installation Instructions Manual

TREND IQECO31/230 Installation Instructions Manual

Bacnet ms/tp terminal unit controller

Advertisement

Quick Links

BACnet MS/TP Terminal Unit Controller
Important: Retain these instructions
These instructions shall be used by trained service
personnel only.
If the equipment is used in a manner not
specified by these instructions, the protection provided by the
equipment may be impaired.
CONTENTS
1

Box contents ..................................................................1

2
Storing ...........................................................................1
1
BOX CONTENTS
3
Labels used on IQ
ECO31/230
Service button
Connector for auxiliary power output
36 35
+V
C
AUX
Connector for Wallbus displays
WMB
31 32
Connector for MS/TP trunk
Connector for USB
Connector for 230 Vac input power.
230 VAC
L
N
!
1
2
3
Connector for Universal Input
n
C
Connector for Digital Input
n
C
Connector for Thermistor Input
n
T
C
Connector for Analogue Output
n
C
3.1
Dimensions
1
IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
Installation Instructions - Mounting
https://partners.trendcontrols.com
3
3.1
4
6
2
IQECO31/230
(-40 °F)
Installation Instructions
- Mounting (TG201224)
Note: For temperatures below zero special care must be taken
that there is no condensation on or within the unit.
MS/TP Network
This product should be connected to a BACnet MS/TP
network. The network installation requirements are different
from an IQL on its L
5
1
OK
!
205 mm (8.07")
189 mm (7.44")
IQECO31/230
Installation .....................................................................1
Installation - Mounting ...................................................1
Cleaning And Maintenance .........................................11
Disposal .......................................................................11
STORING
-40 °C
+60 °C
(140 °F)
H O
2
It is recommended that the installation should comply
with the local electrical safety installation practices (e.g.
HSE Memorandum of Guidance on Electricity at Work
Regulations 1989, USA National Electric Code).
W
®
ON
ORKS
WARNING Removal of cover exposes dangerous
voltages.
Connector for Solid State Digital Output
C
Connector for High Current Relay Output
MSTP OK LED
Caution, consult documentation
Caution, possibility of electric shock
63 mm (2.48")
0
95 %RH
network.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IQECO31/230 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TREND IQECO31/230

  • Page 1 MSTP OK LED Connector for Analogue Output Caution, consult documentation Caution, possibility of electric shock Installation - Mounting Dimensions 63 mm (2.48”) 205 mm (8.07”) 189 mm (7.44”) IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 2 -40 °C (-40 °F) +40 °C (+104 °F) Lift Hinged Covers CAUTION: Failure to use a screwdriver to open the cover will cause damage to the unit. IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 3 5 A circuit breaker with high breaking capacity may be used as an alternative. Do not position the equipment so that the disconnecting device is diffi cult to operate. DO NOT SWITCH ON POWER IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 4 IQECO 31, 32, 35, 38 Data Sheet (TA201176) to calculate available current. WARNING: Do not connect output of an external supply to the AUX output terminals. IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 5 14 (subject to power loading - refer to device documentation and controller memory). Wallbus device IQECO Configuration Manual (TE201089) Polarity independent to additional IQECO IQECO wallbus devices IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 6 Open Contact Collector/Drain 25 26 25 26 25 26 25 26 25 26 0 to 10 V Ensure correct polarity Ensure correct polarity External Power Supply IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 7 120 ohms (nominally) network biassing. Failure to comply with these practices will result significant impairment communication performance. IQECO31/230 BACnet MS/TP Terminal Unit Controller Installation Instructions - Mounting TG201224 Issue 13, 13-Jan-2021.
  • Page 8 Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.