Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
Note: Unavailable models are A6T6 with 2A0002, A6T15 with 2A0004 or
4A0004, A6T20 with 4A0005, and A6T25 with 4A0007.
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Non-Time Delay
Model
Class-T Fuse Type
CIMR-JC
(Manufacturer: Ferraz)
BA0001
BA0002
BA0003
BA0006
BA0010
2A0001
2A0002
2A0004
2A0006
2A0008
2A0010
2A0012
2A0018
2A0020
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide
Fuse Ampere
Rating (A)
Single-Phase 200 V Class
A6T6
A6T10
A6T20
A6T40
A6T40
Three-Phase 200 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T30
A6T40
A6T40
Three-Phase 400 V Class
A6T3
A6T6
A6T15
A6T20
A6T25
A6T25
A6T30
3 Electrical Installation
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
6
FWH-25A14F
10
FWH-25A14F
20
FWH-60B
40
FWH-80B
40
FWH-100B
3
FWH-25A14F
6
FWH-25A14F
15
FWH-25A14F
20
FWH-25A14F
25
FWH-70B
25
FWH-70B
30
FWH-70B
40
FWH-90B
40
FWH-90B
3
FWH-40B
6
FWH-40B
15
FWH-50B
20
FWH-70B
25
FWH-70B
25
FWH-90B
30
FWH-90B
Fuse Ampere
Rating (A)
25
25
60
80
100
25
25
25
25
70
70
70
90
90
40
40
50
70
70
90
90
EN 13

Advertisement