7.3
B3V137 Connections
230V
connection
TA
thermostat
M1
DC inverter fan motor
S1
grill safety micro-switch
water solenoid valve (230V/ 50Hz 1A output
Y1
voltage)
B3V137
7.4
Warnings table
The board provides diagnostics in the event of anomalies,
which can be interpreted from combinations of LEDs.
The following table summarises the warnings.
•
Flashing LED
: TA contact open
•
Flashing LED
: TA contact closed;
•
4 flashing LEDs: S1 contact open;
•
LED on: supersilent speed active (400 rpm).
•
LED on: minimum speed active (680 rpm).
•
LED on: medium speed active (1,100 rpm).
•
LED on: maximum speed active (1,500 rpm).
22
All manuals and user guides at all-guides.com
permission
from
room
L-N
230V/50Hz electrical power supply
RS
RS version cabling
output for mobile suction panel servo (power
FF
output 230V/ 50Hz 1A)
HRS
water probe for RS version (10 kΩ)
N276663A
U
I
S