Ferroli BLUEHELIX THETA C Manual page 87

Table of Contents

Advertisement

Available languages

Available languages

BLUEHELIX THETA C
Fault code
Fault
No flame after the ignition
A06
phase
F15 - A07
High fume temperature
Overtemperature protec-
A08
tion intervention
Exchanger protection inter-
A09
vention
Overtemperature protec-
F09
tion intervention
F10
Flow sensor fault
F11
Return sensor fault
F12
DHW sensor fault
F13
Fume probe fault
Fume extraction duct safety
A14
device intervention
F34
Supply voltage under 180V Electric mains trouble
F35
Wrong supply frequency
System filling, with par. b07
A23
= 2, over 5 minutes.
3 remote filling attempts in
A24
24 hours
A26-F20 -F21
Water pressure switch fault
F40-F47-F51
Incorrect system water
F37
pressure
EN
Possible cause
Ionization electrode fault
Flame unstable
air/fume ducts obstructed
Trap blocked
Wrong calibration
The fume probe detects an
excessive temperature
Sensor not correctly positio-
ned on flow pipe or dama-
ged
No water circulation in the
system
Air in the system
No water circulation in the
system
Poor circulation and anoma-
lous flow probe temperature
increase
blocked exchanger
Flow sensor damaged
No water circulation in the
system
Air in the system
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Probe damaged
Wiring shorted
Wiring disconnected
Fault A07 generated 3 times
in the last 24 hours
Electric mains trouble
Loss in system
Loss in system
Wrongly configured parame-
ter
System pressure problems
(transducer)
b06 set to 3
Pressure too low
Water pressure switch
damaged or disconnected
cod. 3540000272 - Rev. 01 - 01/2024
Cure
Check the position of the ionization elec-
trode, free it from any deposits and do a
complete manual calibration, if necessary
replace the electrode.
Check the burner
Remove the obstruction from the flue, fume
extraction ducts, air inlet and terminals
Check the trap and clean it if necessary
Do complete manual calibration.
Check the exchanger
Check the fume probe
Check the flue material parameter
Check the correct positioning and operation
of the heating sensor and replace it if
necessary
Check the circulating pump
Vent the system
Check the circulating pump and heating
system
Vent the system
check the exchanger and system
Check correct positioning and operation of
the flow sensor and replace it if necessary
Check the circulating pump and heating
system
Vent the system
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the fume probe
See fault A07
Check the electrical system
Check the electrical system
Check the system or the filling valve
Check the system
Check if parameter b04 is configured
correctly (default 0=pressure switch)
System pressure value outside set limits
(transducer)
Fill the system
Check the water pressure switch
87