BLUEHELIX THETA C
System water pressure adjustment
The filling pressure read on the boiler water
gauge (detail 2 - fig. 16) with system cold
must be approx 1.0 bar. If the system pres-
1
sure falls below minimum values, the boiler
stops and fault F37 is displayed. Pull out the
filling knob (detail 1 - fig. 16) and turn it anti-
clockwise to return it to the initial value. Al-
2
ways close it afterwards.
Once the system pressure is restored, the
boiler will activate the 300-second air vent-
ing cycle indicated on the display by Fh.
To prevent boiler shutdown, it is advisable to
periodically check the pressure on the
gauge with system cold. In case of a pres-
sure below 0.8 bar, it is advisable to restore
it.
fig. 16- Filling knob
System draining
The drain cock ring nut is located under the
safety valve inside the boiler.
To drain the system, turn the ring nut (ref. 3
- fig. 17) counter-clockwise to open the
cock. Do not use any tools; use hands only.
To drain only the water in the boiler, first
close the shut-off valves between the sys-
tem and boiler before turning the ring nut.
3
fig. 17
60
EN
cod. 3540000272 - Rev. 01 - 01/2024