Hussmann VR3-M-EP Installation & Operation Manual page 43

Meat/fish remote
Table of Contents

Advertisement

Troubleshooting Cont'd
Problem
Case temperature is
too warm.
Case temperature is
too cold.
Condensation on
glass.
Water has pooled
under case.
Case is not draining
properly.
Frost or ice on
evaporator coil.
Possible Cause
Ambient conditions may
be affecting the case
operation.
Discharge air temp is out
of spec.
Case is in defrost.
Product load may be over
its limits blocking airflow.
The t-stat temp is set too
low.
Ambient conditions may
be affecting the case
operation.
Ambient conditions may
be affecting the case
operation.
There are glass gaps on
the side of the case.
Glass is not completely
shut.
Ambient Conditions
Case drain is clogged.
PVC drains under case
may have a leak.
Case tub has unsealed
opening.
If the case is in a line-
up, case to case joint is
missing or unsealed.
Evaporator pan is
overflowing (if applicable).
Case is not level.
Drain screen is plugged.
Drain or P-trap is clogged. Clear any debris.
Defrost clock is not
functioning.
Possible Solution
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at or below 75°F Dry bulb and 55% relative humidity.
Check suction pressure and insure that it meets factory
specifications.
Check defrost settings. See Technical Specifications section.
Redistribute product so it does not exceed load level.
Check settings. See Technical Specifications section.
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at or below 75°F Dry bulb and 55% relative humidity.
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at or below 75°F Dry bulb and 55% relative humidity.
See glass adjustment section.
Close glass correctly.
Turn on Air Sweep Fans located at the right rear of
merchandiser.
Clear drain.
Repair as needed.
Seal as needed.
Install case to case joint and seal as needed.
Check electrical connection to evaporator pan. Check float
assembly, it should move freely up and down the support
stem. Clear any debris.
Level the case.
Clean drain screen and remove any debris.
Case should be serviced by a qualified service technician.
43