Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Measuring circuit for measuring the current detector
The minimum current necessary for the control box operation is
1 µA. The burner normally supplies a higher current value, so that
no check is needed.
Anyway, if you want to measure the ionisation current, you need
to open the connector (CN1) fitted on the red wire and insert a mi-
croammeter.
Flame control
Displayed value:
MIN
1 µA
= 20%
MAX
40 µA = 100%
This display is possible only in operating mode or
in stand-by!
WARNING
LME7...
X10-05/2
X10-05/1
S8615
Key (Fig. 165)
C
Electrolytic capacitor 100...470 µF; DC 10...25 V
ION
Ionisation probe
M Microammeter Ri max. 5,000 
8.3

Opening and closing the burner

Turn off the burner's power supply using the main
system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Maintenance
M
C
ION
Fig. 165
55
Combustion
In case the combustion values found at the beginning of the inter-
vention do not respect the standards in force or, in any case, do
not correspond to a proper combustion, contact the Technical As-
sistance Service in order to carry out the necessary adjustments.
MIN output
CO
(%)
2
Methane
8
LPG
9.5
G25
7.8
8.2.4

Safety components

The safety components should be replaced at the end of their life
cycle indicated in Tab. S. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment condi-
tions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Hoses (if present)
Fan impeller
Wait for the components in contact with heat
sources to cool down completely.
After carrying out maintenance, cleaning or
checking operations, reassemble the cover and
all the safety and protection devices of the burner.
GB
MAX output
O
(%)
CO
(%)
O
2
2
6.6
8.5
6.4
10
6.8
8.3
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000
pressurised cycles
10 years or 500,000 start-ups
(%)
2
5.7
5.6
5.8
Tab. R
Tab. S
20160576

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx 250 s/pvRx 180 s/pv903t42016002120160022

Table of Contents