9.3.2
Before starting with a new program module or
when the program module is replaced
Alternatively
nfo
> 3s
Alternatively
Alternatively
nfo
> 1s
At the first start-up or after replacing the pro-
gram module, after the completion of the re-
store process the sequence of the functions
and
the
parameter
WARNING
checked.
20160576
Operation, indications, diagnostic
The display shows rSt and PrC alternately.
The display shows the replacement of the program module.
The indicator light blinks alternately one red and two yellow.
nfo
Press
for >3 to start the download of the program module data.
The indicator light blinks yellow.
The process that lasts 3 seconds is accompanied by short yellow blinking.
nfo
Note:
If you press
for <3 seconds, the download does not start. To restart the reset process, you need
to reset the LME7... switching the mains ON/OFF.
The display shows 'run' during the download (reset process) of the program sequence.
The display shows rSt and End alternately.
The display shows the end of the data exchange.
After 2 minutes, the unit passes to Loc 138
At the end of the reset process, the unit is automatically in a lockout position (LOC 138) and need to
be released in order to work!
nfo
Press
for >1 second to release the unit.
Display: OFF
settings
should
be
60
GB
Tab. X