Riello 908T4 Installation, Use And Maintenance Instructions page 18

Premix gas burners
Table of Contents

Advertisement

Installation notes
 Arrange the high voltage ignition cables separately, as far as
possible from the control box and the other cables.
 Do not confuse the powered conductors with the neutral
ones.
 Install the switches, fuses and grounding in compliance with
local regulations.
 The connection diagrams show the burner controls with
grounded neutral conductor.
 Make sure that the maximum admissible current of the termi-
nal connections is not exceeded.
 Make sure the cable grommets of the connected cables
comply with the relevant standards.
 Do not supply mains voltage to the control box outputs. Dur-
ing the testing of the devices controlled from the burner con-
trol (fuel valve, etc), the LME71... should not be connected
to the units.
 The mechanical connection between the actuators and the
fuel and air control elements, or any other type, should be
rigid.
 Make sure there are no short-circuits on the air pressure
switch connection lines.
Electrical wiring to the flame detectors
It is important for signal transmission to be practically free of any
disturbances or loss:
 Always separate the detector cables from the other cables:
– the capacitive reactance of the line reduces the magnitude
of the flame signal;
– use a separate cable.
 Respect the permitted lengths for the cables of the detectors
(see Technical Data).
 The ionisation probe powered from the mains is not pro-
tected from the risk of electric shocks.
 Position the ignition electrode and the ionisation probe so
that the ignition spark cannot form an arc on the probe (risk
of electric overload) and that it cannot negatively effect the
supervision of the ionisation.
20160576
Technical description of the burner
16
GB
Description of displays and buttons
A
S8595
Button
Function
Button A
A
Displaying default output
In lockout position: output value at the time of
the fault
Enter and Info button
nfo
The reset button (info button) is the key element
for resetting the burner control and activating/de-
activating the diagnostic functions.
Button -
-
Displaying flame 2 signal current or display-
ing phases
In lockout position: MMI phase at the time of
the fault
Button +
+
Displaying flame 1 signal current or display-
ing phases
In lockout position: MMI phase at the time of
the fault
Warning light with 3 colours
The warning light with three colours (red - yellow
- green) is the key indicator of the visual diagnos-
tics.
Button + and -: escape function
-
+
Press the + and - buttons at the same time!
No adoption of value
and
Access to a higher menu level
Keep pressed for >1 second for the backup/
reset function
-
+
nfo
Fig. 11
Tab. F