Checking The Air And Gas Pressure On The Combustion Head; Safety Components - Riello RS 68/E O2 ULX Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Gas leaks
Make sure that there are no gas leaks on the pipes between the
gas meter and the burner.
Gas filter
Replace the gas filter when it is dirty.
Flame inspection window
Clean the glass of the flame inspection window.
Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics intact,
especially the flue gas temperature and combustion chamber
pressure.
Electric current to the flame sensor
Clean the ionization probe from any dust.
Check the mechanical integrity of the component and the flame
signal measured by the control box.
Combustion
If the combustion values found at the start of the intervention do
not satisfy current standards or anyway indicate a poor state of
combustion (consult the table below), contact the Technical As-
sistance Service for the necessary adjustments.
EN 676
Max. output
CO
CO
theoretic
2
2
GAS
al max. 0% O
 = 1.2
2
G 20
11.7
9.7
G 25
11.5
9.5
Electric current to the flame sensor
Clean the ionization probe from any dust.
Check the mechanical integrity of the component and the flame
signal measured by the control box.
20205911
Air excess
Min. output
  1.2
  1.3
% Calibration
CO
 = 1.3
mg/kWh mg/kWh
9.0
 100
8.8
 100
Maintenance
6.2.4
Checking the air and gas pressure on the
combustion head
To carry out this operation a pressure gauge must be used to
measure the air and gas pressure at the combustion head, as
shown in Fig. 38.
6.2.5

Safety components

The safety components should be replaced at the end of their life
NO
X
cycle indicated in Tab. Q.
The specified life cycles do not refer to the warranty terms indi-
 170
cated in the delivery or payment conditions.
 170
Safety component
Tab. P
Flame control
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor
(electronic cam) (if present)
Oil valve (solenoid)
(if present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Fan impeller
42
GB
+
_ _
Checking
Checking
air pressure
gas pressure
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
10 years or 500,000 start-ups
20209399
+
_
Fig. 38
Tab. Q

Advertisement

Table of Contents
loading

Table of Contents