Maintenance
6.1
Problems and remedies
If the burner does not work properly, first you must:
1
check that the electric connections have been correctly performed;
2
ensure that the fuel is delivered correctly;
3
check that all the adjustment parameters (e.g. boiler water temperature or boiler steam pressure) are correctly set.
Fault
The burner does not start
The burner does not start and a
function lock out occurs
The burner ignites but then
blocks
The burner starts and then locks
out
After pre-purge and safety time,
the burner goes to lock-out and
the flame does not appear
The burner goes to lock-out right
after flame appearance
Possible cause
• No electrical power supply . . . . . . . . . . . . . . . . . . . .Close all switches - Check connec-
• A limiter or safety control device is open. . . . . . . . . .Adjust or replace
• Flame control lock-out. . . . . . . . . . . . . . . . . . . . . . . .Reset control box
• Control box fuses blown . . . . . . . . . . . . . . . . . . . . . .Replace
• Erroneous electrical connections . . . . . . . . . . . . . . .Check connections
• Defective flame control . . . . . . . . . . . . . . . . . . . . . . .Replace
• No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Open the manual valves between
• Mains gas pressure insufficient. . . . . . . . . . . . . . . . .Contact your GAS COMPANY
• Minimum gas pressure switch fails to close . . . . . . .Adjust or replace
• Air pressure switch in operating position . . . . . . . . .Adjust or replace
• Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . .Replace control box
Air pressure switch inoperative due to insufficient air pressure:
• Air pressure switch adjusted badly . . . . . . . . . . . . . .Adjust or replace
• Pressure switch pressure point pipe blocked . . . . . .Clean
is blocked
• Head wrong adjusted . . . . . . . . . . . . . . . . . . . . . . . .Adjust
• Fault in flame detection circuit . . . . . . . . . . . . . . . . .Replace flame control
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Solenoid valves VR or VS fail to open . . . . . . . . . . .Renew the coil or rectifier panel
• Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . .Increase on the regulator
• Defective ignition transformer . . . . . . . . . . . . . . . . .Replace
• Erroneous valve or transformer electrical . . . . . . . .Repeat connections
connections
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace
• A cock down-line of the gas train is closed . . . . . . . .Open
• Air in pipework . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bleed air
• The solenoid VR allows little gas through . . . . . . . . .Increase
• Max. gas pressure switch operates. . . . . . . . . . . . . .Adjust or replace
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . .Replace