Riello 46662X Installation, Use And Maintenance Instructions page 32

Industrial gas burners
Table of Contents

Advertisement

Available languages

Available languages

3.4
Accessibility to the interior of the combustion head
20069041
Switch off the electrical power.
Remove the fixing screws 11).
Remove the 8 fixing screws 1) and the protections 3-4).
Unscrew the locknuts 6) and release the tie rod 7, open the air suction duct 12) on the hinge after disconnecting it from ventil
connection.
Disconnect the electrode wires 2) of ignition pilot 14).
Disconnect the ignition pilot 14) unscrew the connector 15).
Unscrew the screw 8) with pressure gauge.
Extract the internal part 13) of the combustion head.
With burner closed, the accessibility to the interior combustion head is possible by removing the cover 12).