Main Frequency Reference Setting Channel Selection; Max. Frequency; Frequency Reference Upper Limit; Frequency Reference Lower Limit - Trane RTXC-XE Series Installation, Operation And Maintenance Manual

Air-cooled screw chiller heat pump
Table of Contents

Advertisement

RTXC-SVX003D-EN
Para. No.
Para. Name
Main frequency reference
F0-03
setting channel selection
Auxiliary frequency
F0-04
reference setting channel
selection
Base value of range of
auxiliary frequency
F0-05
reference for main and
auxiliary superposition
Range of auxiliary frequency
F0-06
reference for main and
auxiliary superposition
Final frequency reference
F0-07
setting selection
F0-08
Preset frequency
F0-09
Running direction
F0-10

Max. frequency

Setting channel of frequency
F0-11
reference upper limit
Frequency reference upper
F0-12
limit
Frequency reference upper
F0-13
limit offset
Frequency reference lower
F0-14
limit
F0-15

Carrier frequency

Carrier frequency adjusted
F0-16
with temperature
F0-17

Acceleration time 1

F0-18

Deceleration time 1

Acceleration/ Deceleration
F0-19
time unit
Frequency offset of auxiliary
frequency setting channel
F0-21
for main and auxiliary
calculation
Setting Range
Group F0: Standard Parameters
0: Digital setting F0-08
(pressing UP or DOWN can
revise F0-08 easily, but the
revised value would be cleared
after power off)
1: Digital setting F0-08
(pressing UP or DOWN can
change F0-08 easily, and the
revised value won't be cleared
even after power off)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting
10: Reserved
Same as F0-03
0: Relative to maximum
frequency
1: Relative to main frequency
reference
0% to 150%
Ones position: Frequency
reference selection
0: Main frequency reference
1: Main and auxiliary calculation
(based on tens position)
2: Switchover between main and
auxiliary
3: Switchover between main and
"main & auxiliary calculation"
4: Switchover between auxiliary
and "main & auxiliary
calculation"
Tens position: Main and auxiliary
calculation formula
0: Main + auxiliary
1: Main - auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x auxiliary
0.00 Hz to max. frequency (F0-
10)
0: Run in the same direction
1: Run in opposite direction
50.00 to 600.00 Hz
0: Set by F0-12
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication setting
6: Multi-reference
Frequency lower limit (F0-14) to
max. frequency (F0-10)
0.00 Hz to max. frequency (F0-
10)
0.00 Hz to frequency upper limit
(F0-12)
2 to 8.0 kHz
0: Disabled
1: Enabled
0.00s~650.00s (F0-19=2)
0.0s~6500.0s (F0-19=1)
0s~65000s (F0-19=0)
0.00s~650.00s (F0-19=2)
0.0s~6500.0s (F0-19=1)
0s~65000s (F0-19=0)
0: 1s
1: 0.1s
2: 0.01s
0.00 Hz to max. frequency (F0-
10)
Default
Property
0
0
0
100%
0
50.00 Hz
0
50.00 Hz
0
50.00 Hz
0.00 Hz
0.00 Hz
Model
dependent
1
20.0s
20.0s
0.00 Hz
75

Advertisement