Huawei SUN2000-111KTL-NHM0 User Manual page 124

Hide thumbs Also See for SUN2000-111KTL-NHM0:
Table of Contents

Advertisement

SUN2000-111KTL-NHM0
User Manual
Alarm
Alarm
ID
Name
2063
Cabinet
Overtempe
rature
2064
Device
Fault
2065
Upgrade
Failed or
Software
Version
Unmatch
Issue 09 (2023-12-18)
Alarm
Possible Causes
Severity
Minor
Cause ID = 1
1. The solar inverter is installed in
a place with poor ventilation.
2. The ambient temperature is too
high.
3. The solar inverter is not
working properly.
Major
Cause ID = 1, 2-5, 7-12, 20
A fault occurs on the internal
inverter circuit.
Minor
Cause ID = 1–4
The upgrade does not complete
normally.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Suggestions
1. Check the ventilation
and whether the
ambient temperature
of the solar inverter
exceeds the upper
limit. If the ventilation
is poor or the ambient
temperature is too
high, improve
ventilation.
2. If both the ventilation
and ambient
temperature meet
requirements yet the
fault persists, contact
your dealer or
technical support.
● Cause ID = 1
Contact your vendor or
technical support, wait
until the PV string
current decreases to
below 0.5 A, and then
turn off all DC
switches.
● Cause ID = 2-5, 7-12
Turn off the AC output
switch and then the
DC input switches.
After 5 minutes, turn
them on in the same
sequence. If the fault
persists, contact
technical support.
● Cause ID = 20
Do not turn on the DC
input switch. Contact
your vendor or
technical support.
1. Perform an upgrade
again.
2. If the upgrade fails for
multiple times, contact
your dealer or
technical support.
116