Alarm
Alarm
ID
Name
2036
Grid
Overfreque
ncy
Issue 09 (2023-12-18)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
Power grid exception: The actual
power grid frequency is higher
than the standard requirement for
the local power grid.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Suggestions
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The solar
inverter automatically
recovers after
detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check
whether the power
grid frequency is
within the acceptable
range. If not, contact
the local power
operator. If yes, log in
to the mobile phone
app, SmartLogger, or
NMS to modify the
power grid
overfrequency
protection threshold
with the consent of
the local power
operator.