Alarm
Alarm
ID
Name
2034
Grid
Overvoltag
e
2035
Grid Volt.
Imbalance
Issue 09 (2023-12-18)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
The grid voltage exceeds the
upper threshold or the
overvoltage duration exceeds the
time that triggers high voltage
ride-through (HVRT).
Major
Cause ID = 1
The difference between grid phase
voltages exceeds the upper
threshold.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Suggestions
1. Check whether the
grid connection
voltage exceeds the
upper threshold. If yes,
contact the local
power operator.
2. If you have confirmed
that the grid
connection voltage
exceeds the upper
threshold and have
obtained the consent
of the local power
operator, modify the
overvoltage protection
threshold.
3. Check whether the
peak grid voltage
exceeds the upper
threshold.
1. Check that the grid
voltage is within the
normal range.
2. Check that the AC
output power cable is
correctly connected. If
the AC output power
cable is correctly
connected, yet the
alarm persists and
affects the energy
yield of the PV plant,
contact the local
power operator.
111