7 VSD Standardization

Motor standardization (speed acquisition) allows the LMV unit to control the motor rounds at the maximum frequency signal coming from the VSD. A
temporary standardization is factory set only for test purpose. The definite standardization must be performed on site by the Service Center (only if the
fan is supplied), before the plant test.
ATTENTION: To perform standardization, the burner must be in stand-by mode, not it lockout stage. The Safety loop must be
closed (X3-04).
Following the below route access to the programming levels of the menu by means the Esc
1st level
2nd level
Params & Display
VSD Module
By activating the standardization, without starting the burner up, the air actuator drives to ites maximum opening. Then the fan motor stars and the VSD
drives the motor to its maximum speed. The speed sensor, mounted on the motor, detects the rpm value. LMV stores the data and the motor stops.
ATTENTION: do not enter manually the rpm value of the motor data plate on parameter "StandardizedSp".
ATTENTION: the power cable that connects VSD to motor must be screened.
3rd level
4th level
Configuration
Speed
5th level
Standardization
Deactivated
Activated
24
Range
Description
Menu level for making the
parameter settings
Settings for the VSD
module
Standardization process for
fan speed