check the fan motor rotation (see related paragraph).
4
make the safety chain enabling the system to start up
5
the combustion cycle starts: the system will show the operating stages
- Prepurging (program phase no.30)
- Driving to ignition position (program phase no.36)
- Ignition position (program phase no.38)
- Fuel (the fuel solenoid valves open)
- Flame (the flame lights up)
- Driving to low flame (the actuator drives to low flame).
NOTE: the C and A, on the .
Once the ignition cycle ends, the main page is shown:
Set point: temperature set-point
Act value: actual temperature value
Load: load percentage (burner output)
Flame: percentage of flame detection current.
By pressing the ENTER key the display shows the second page:
Fuel: it shows (in degrees) the fuel actuator position.
Air: it shows (in degrees) the air actuator position.
Ax1..3: auxiliaries.
VSD: % value on the inverter maximum frequency
O2: oxygen percentage
Ld: load percentage (burner output).
Press the ENTER key to go back to the main page.
To access the main menu, from the main page, press the ESC key tiwce:
Setpoint
Act.value
Fuel
Standby
Main page
Setpoint
Act.value
Load
Flame
Main page
Fuel
0.0
Ax
Ax
Ax
Second page
OperationalStat
Operation
ManualOperation
Params & Display
Main menu
33
80°C
78°C
GAS
12
80°C
78°C
24%
60%
Air
1.8
VSD
0.0
O2
Ld.
0.0
PART III: OPERATION