Assembling the light oil flexible hoses
To connect the flexible light oil hoses to the pump, proceed as follows, according to the pump provided:
1
remove the closing nuts A and R on the inlet and return connections of the pump;
2
screw the rotating nut of the two flexible hoses on the pump being careful to avoid exchanging the inlet and return lines: see
the arrows marked on the pump that show the inlet and the return (see prevoius paragraph).
Suntec TA..
A
Diesel filters
5
6
7
(*) Supplied per pilot diesel fuel if present
R
Item
Note
20151PE (*)
-
20201PL (*)
-
GA70501
-
Suntec T
R
A
Connection
Max. operating
pressure
3/8"
1 bar
3/8"
1 bar
1"
4 bar
27
PART II: INSTALLATION
HP Technik UHE
A
R
Max. operating
Filtering
temperature
degree
-20, 60 °C
100 μ
-20, 60 °C
100 μ
90 °C
100 μ
Protec-
tion
-
-
IP65