Diagnostics - Brant Radiant Heaters DX2 Series Manual

Gas-fired infrared tube heater
Table of Contents

Advertisement

DX2
Series

Diagnostics

Lockout:
The controls will automatically lockout the heater system when an external or system fault occurs. There
are two types of lockout:
Soft Lockout: The heater will attempt to light three times. In the event of a failed attempt to light, (gas
pressure, valve, no flame sense etc.), the heater will enter a soft lockout period for 15
minutes and then attempt to light three more times before entering Hard Lockout mode.
Hard Lockout: If proof of flame is not established, a component failure occurs or blockages are evident,
the heater will enter hard lockout. If lockout occurs, the control can be reset by briefly
interrupting the power source.
Operational Indicator Lights
The externally located operational indicator lights are provided to assist in troubleshooting of the heater.
Refer to the following pages for additional troubleshooting.
Figure 4.1
Operational Indicator Lights
4.0
Operation
Diagnostics
V
VALVE
Light 1
Indicates Valve
Opens
Operational Indicator Lights
53
Operational Indicator Lights
PS
PRESSURE
SWITCH
Light 2
Indicates Pressure
Switch Closes