3.0
Installation
Hanger Placement and Suspension
Figure 3.6
U-Tube Hanger Mounting Options
U-Tubes can be mounted from a single suspension
point using a Single Mounting Bracket (P/N: SMB)
with five S-hooks and #1 double-loop chains.
Figure 3.7
Angled Hanger Mounting Options
For 45 degree hanging angle use two
S-hooks and two #1 double-loop chains.
Single Mounting
Bracket
U-Tubes can be mounted at a
15, 30 or 45 degree angle with two
suspension points, using two Brass Knuckle
(P/N: BK) fittings, #1 double-loop chains and
S-hooks.
For variety of hanging angles, use the Brass
Knuckle (P/N: BK) fitting with a #1 double-
loop chain and S-hook.
18