Testing for gas leaks with an open flame or other sources of ignition may lead to a fire or
explosion and cause serious injury or death. Test in accordance with NFPA or local codes.
Figure 3.31
Gas Connection (Flexable Gas
Connection shown) - Side View
NOTE: Do not exceed 14 inches W.C to the appliance.
Adapter
12"
(30cm)
Adapter
Rubber Hose Gas Connector,
formed into a C-shape
*The tube heater expands and contracts during operation. Follow the installation instructions to ensure
allowances are made for this movement. To ensure your safety, and comply with the terms of the
warranty, all units must be installed in accordance with these instructions.
WARNING
!
Ball Valve / Inlet Tap
Drip Leg/
Sedement Trap
3" (7.62cm) max displacement
Heater Movement
Figure 3.32
Connection shown) - End View
Ball Valve / Inlet Tap
Burner
Control Box
Burner Control Box
41
3.0
Installation
Gas Connection (Flexable Gas
45
o
Horizontal
Remove cap to
clean sediment trap
Gas Supply