Monitoring temperatures
and system units - line B
Controlled units
1
1
2
B
ON
DHW
storage
tank temp.,
center
4
0
sensor (S4)
Push and hold the shift button to see:
- the desired DHW storage tank temperature.
The activity of controlled units is shown as blanks (OFF) or ON
/ arrow up when the unit is ON.
If a sensor is not mounted or is disconnected, the display will
indicate it as "- -".
If the sensor is short-circuited, the display will indicate
it as "- - -".
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
°C
1600
-50
805
1500
-40
845
-30
883
-20
922
1400
-10
961
0
1000
1300
10
1039
20
1078
30
1117
1200
40
1155
50
1194
1100
60
1232
70
1271
1000
80
1309
90
1347
100
1385
900
110
1423
120
1462
800
130
1501
140
1539
150
1578
-50
-25
The grey
side of the
ECL Card
2
3
ON
DHW
storage
tank temp.,
lower
3
0
sensor (S5)
0
25
50
75
100
125
150
Manual control -
line B
Shift to manual mode.
Choose the unit you want to control. The selected
unit symbol will blink.
Controlled units are switched OFF or ON when the
relevant button is pushed.
During manual operation, all control functions are deactivated.
°C
Controlled units
1
1
2
2
3
Controller mode
B
ON
ON
4
0
3
0
19
The grey
side of the
ECL Card