Monitoring Temperatures And System Units - Line B; Manual Control - Line B - Danfoss ECL Comfort 300 User Manual

Hide thumbs Also See for ECL Comfort 300:
Table of Contents

Advertisement

18
Monitoring temperatures
and system units - line B
Controlled units
1
1
B
ON
Flow
1
2
temp.
(S3)
Push and hold the shift button to see:
- the calculated flow temperature
- the desired return temperature limitation.
The activity of the motorized control valve is shown as arrows
below the valve symbol. When the circulation pump is
operating, it is indicated as ON below the pump symbol.
If a sensor is not mounted or is disconnected, the display will
indicate it as "- -".
If the sensor is short-circuited, the display will indicate
it as "- - -".
If you are in doubt, remove the controller and check the
ohmic value between the relevant terminals.
Relationship between temperature and ohmic value
°C
1600
-50
805
1500
-40
845
-30
883
-20
922
1400
-10
961
0
1000
1300
10
1039
20
1078
30
1117
1200
40
1155
50
1194
1100
60
1232
70
1271
1000
80
1309
90
1347
100
1385
900
110
1423
120
1462
800
130
1501
140
1539
150
1578
-50
-25
The grey
side of the
ECL Card
3
Return
1
5
temp.
(S4)
°C
0
25
50
75
100
125
150
Manual control -
line B
Shift to manual mode.
Controlled units
1
1
B
ON
1
2
Choose the unit you want to control. The selected
unit symbol will blink.
Controlled units are switched
the relevant button is pushed.
The motorized actuator (gear motor)
closes
or opens
the relevant button is pushed. If pushed for more
than 3 seconds, the actuator continues to close or
open the valve.
Check the activation direction of the actuator either by
looking at it or by feeling whether the temperature of the
actual pipe changes as expected.
This operation applies to both circuits, if available.
During manual operation, all control functions are deactivated.
19
3
Controller mode
1
5
OFF or ON when
the controlled unit as long as
The grey
side of the
ECL Card

Advertisement

Table of Contents
loading

Table of Contents