9.2.3

First inspection after installation or repair

Perform the following checks after approximately 500 operating hours or at the latest six
months after commissioning:
Table 9-1
Checking
The electrical parameters are maintained.
The permissible bearing and winding temperatures are not exceeded.
The smooth running characteristics and machine running noise have not de‐
teriorated.
The foundation has no cracks or indentations. (*)
(*) You can perform these checks while the motor is running or at a standstill.
Additional tests may also be required according to the system-specific conditions.
NOTICE
Machine damage
When carrying out the inspection, if you detect any impermissible deviations from the normal
state, you must rectify them immediately. They may otherwise cause damage to the machine.
9.2.4

General inspection

Check that the installation conditions are observed. We recommend doing this after approx.
16 000 operating hours. Check the following at the latest after 2 years:
Table 9-2
Checking
The electrical parameters are maintained.
The permissible bearing temperatures are not exceeded.
The smooth running characteristics and machine running noise have not de‐
teriorated.
The foundation has no cracks or indentations. (*)
The machine is aligned within the permissible tolerance ranges
All the fixing bolts/screws for the mechanical and electrical connections have
been securely tightened
All the potential connections, grounding connections and shield supports are
correctly seated and properly bonded
The winding insulation resistances are sufficiently high
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 11/2023, A5E52779900A
Checks after assembly or repair
Checks that have to be performed during the general inspection
Maintenance
9.2 Inspection and maintenance
When the
At stand‐
motor is
still
running
X
X
X
X
When the
At stand‐
motor is
still
running
X
X
X
X
 
 
 
 
 
 
 
X
 
 
 
X
X
X
X
X