Stud-Type Bushings; Terminal Boxes, End Shields, Grounding Conductors, Sheet Metal Fan Covers; Terminal Board And Grounding; Tightening Torques Of Additional Connecting Terminals - Siemens SIMOTICS XP 1MB 1 Series Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Technical data
A.1 Tightening torques
Non-standard tightening torques
Different tightening torques for electrical connections and bolted connections for parts with
flat seals or insulating parts are specified in the relevant sections and drawings.
A.1.2

Stud-type bushings

Table A-2
Tightening torques for stud-type bushings
Thread ∅
Min.
Nm
Max.
A.1.3

Terminal boxes, end shields, grounding conductors, sheet metal fan covers

If no other tightening torques are specified, then the values in the following table apply.
Table A-3
Tightening torques for screws on the terminal box, end shields, screw-type grounding conductor connections
Thread ∅
M3.5
Nm
min.
0.8
max.
1.2
Tightening torque for the condensation drain plug
Tighten the condensation drain plug M6x0.75 with a torque between 1.5 and 2.0 Nm.
A.1.3.1

Terminal board and grounding

Table A-4
Tightening torques for electrical connections on the terminal board and grounding
Thread ∅
M3.5
min.
0.8
Nm
max.
1.2
A.1.4

Tightening torques of additional connecting terminals

Table A-5
Main terminal box
EN 60999-1: 2000 table 4 III
Auxiliary terminal box
170
M4
M5
M6
1
1.6
2.5
1.2
2
M4
M5
2
3.5
3
5
M4
M5
0.8
1.8
1.2
2.5
Tightening torques for electrical connections of monitoring equipment and anti-
condensation heating
M8
M10
5
8
3
6
10
M6
M8
M10
6
16
9
24
M6
M8
2.7
5.5
4
8
min 0.6 Nm
M12
M16
13
25
15.5
30
M12
M16
28
46
110
42
70
165
M10
M12
9
14
13
20
0.4 Nm
max 0.8 Nm
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 11/2023, A5E52779900A
M20
42
52
M20
225
340
M16
27
40

Advertisement