Power Supply; Connections; Miscellaneous - SCHIEBEL AB3 Operating Instructions Manual

Actuators with control unit
Hide thumbs Also See for AB3:
Table of Contents

Advertisement

Operating Instructions for Actuators Type AB with Control Unit
OM-ENGLISH-ABCSC.V1.2-16xx-V2.02-2023.04.27

15.9 Power supply

The internal supply of the SMARTCON control unit is made via the power connection. At 3-phase current a
neutral phase is not required. The following table shows the possible different voltage ranges of the control.
voltage (3-phase, standard range): . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 380, 400, 415, 440 VAC +/-10%
voltage (3-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 110, 115, 120 VAC +/-10%
voltage (3-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 220, 230, 240 VAC +/-10%
voltage (3-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 460, 480, 500, 525 VAC +/-10%
voltage (3-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 x 575, 660, 690 VAC +/-10%
voltage (single-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110, 115, 120 VAC +/-10%
voltage (single-phase, on request): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220, 230, 240 VAC +/-10%
frequency: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50/60Hz, +/-3Hz
idle power consumption: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .max. 24W
NOTE: For the supply voltage of the complete system (control unit and actuator) also the motor voltage must
still be considered (see actuator data and name plate)!

15.10 Connections

Size 1 (mechanical reversing starter mW4, mW5, mW7K and electronical reversing starter):
Power / motor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . till 440V: Industrial plug with 6 pins, screw connection
Control signals: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial plug with 24 pins, screw connection
optional crimp contacts are available
Size 2 (mechanic reversing starters mW7, mW11 and mW22):
Power / motor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial plug with 4 pins, screw connection
Control signals: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Industrial plug with 24 pins, screw connection
optional crimp contacts for the control unit are available
Explosion-proof version:
Power / motor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminals with screw connection
Control signals: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . terminals with screw connection

15.11 Miscellaneous

Ambient temperature:
On/Off Actuators: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 to +70°C
Modulating actuators: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -25 to +60°C
explosion-proof version: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20 to +40°C (acc. EN60079-0)
protection class:
standard actuators, size 1 1: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP67
standard actuators, size 2: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65
explosion-proof version: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65
colour: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RAL7030 (other colors on request)
2
16A, max. 2,5mm
, AWG14
from 460V: Industrial plug with 3+2 pins, screw connectio
2
16A, max. 2,5mm
, AWG14
2
16A, max. 2,5mm
, AWG14
2
80A, 1,5. . . 16mm
2
16A, max. 2,5mm
, AWG14
2
16A, 0,5. . . 4mm
, AWG20. . . AWG12
2
4A, 0,5. . . 2,5mm
, AWG20. . . AWG14
15 Technical data
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ab80Ab100Ab500Ab5Ab8Ab18 ... Show all

Table of Contents