Operating Instructions for Actuators Type AB with Control Unit
OM-ENGLISH-ABCSC.V1.2-16xx-V2.02-2023.04.27
Figure 37
This changes the bottom line of the display for "SAVE?" to "EDIT?" and the end position is stored.
Figure 40

5.8.2 End limit CLOSE

Use menu item "P 1.2 End limit - End limit CLOSE" as for End limit OPEN

5.9 Setting of the end positions (design for switch for travel)

CAUTION: Depending on the load intensity, special actuators with
high output speed display a trailing effect when switched off. This
must be taken into consideration accordingly when adjusting the
travel switches. The actuator can use either a roller-type counter
or a camshaft gear for travel determination, as need be.

5.9.1 Roller-type Counter (operational range starting at 1 rev. at the output)

• Setting the position „CLOSE":
Move the actuator into the position „CLOSE"by hand. To set the final position, push the flasher shaft with
square cam (see Figure 42) downwards with the finger. Using a screwdriver, turn the slotted shaft of the
"R"rollers in the direction of the arrow, until the corresponding counter-clockwise trip cam activates the
travel switch (see Figure 43). Release flasher shaft and be sure that the toothed roller locks in.
Figure 38
5 Commisioning
Figure 39
Figure 41