Vector MZ3-C-V11 Manual page 6

Controller/positioner for comfort ventilation with integrated co2 sensor
Table of Contents

Advertisement

Configuration
Configuration of the output signal and jumper
If JP1 is in position 1-2, the output signal is 0 VDC in OFF mode
If JP1 is in position 2-3, the output signal remains at level 0 (minimum
volume) in OFF mode according to OP00
The jumper position can be seen in section "View of rear part, without front panel" page 3.
Input configuration (CO2)
Parameter
Description
IP00
Auto operation
- ON: Level mode: Output jumps to the defined level depending on
the input values in: OP00, OP01, OP02 or OP03
- OFF: Continuous mode: Output behaves linear between OP00
and OP03 in Auto mode.
IP01
Samples taken for averaging input signal
IP02
400 ppm Calibration
- 0: Normal, not active
- 1: Start 400 ppm calibration
- 7: Calibration failed
IP03
1)
Automatic Self-Calibration (ASC)
- ON: ASC switched on
- OFF: ASC switched off
IP04
- Level mode: CO2 switching limit of level 1.
- Continuous mode: CO2 start value for continuous control for the
minimum output voltage according to OP00
IP05
- Level mode: CO2 switching limit of level 2.
Note: If this level is set to 0, it is deactivated for level mode.
- Continuous mode: Not used.
IP06
- Level mode: CO2 switching limit of level 3.
Note: If this level is set to 0, it is deactivated for level mode.
- Continuous mode: CO2 end value for continuous control for the
maximum output voltage according to OP03
IP07
CO2 hysteresis of level mode
IP08
Reset time manual to auto operation
0: Never reset
IP09
Altitude (meters above sea level) for pressure compensation of the
CO2 sensor
1)
If IP03 = Off, a manual 400 ppm calibration must be performed regularly. Annual drift ± 5 ppm + 2 % of measured value.
2)
The smallest deactivated level determines up to which level the automatic level mode can regulate.
3)
If IP06 = 0, IP05 is the sensor end value for the maximum output voltage according to OP02.
Output configuration (AO)
Parameter
Description
OP00
Output level 0: 0...100 % = 0...10.0 VDC
OP01
Output level 1: 0...100 % = 0...10.0 VDC
Note: setting a level to 0 disables it
OP02
Output level 2: 0...100 % = 0...10.0 VDC
Note: setting a level to 0 disables it
OP03
Output level 3: 0...100 % = 0...10.0 VDC
Note: setting a level to 0 disables it
OP04
Automatic reset time of the highest level to the level defined in
OP05. The reset is deactivated with setting = 0
OP05
Level after automatic reset. This level will be activated once the
reset time defined in OP04 has expired.
OP06
- 0: Parameter copy successful; No action
- 1: Start parameter copy to AEC-PM2
- 7: Copy fail (no AEC-PM2 or communication error)
Doc: 70-00-0982A V2.5, 20230123
Subject to alternation
3)
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
MZ3-C-V11
Range
ON, OFF
1...255
0...1
7: display only
ON, OFF
400...2000 ppm
400...2000 ppm
1200 ppm
2)
400...2000 ppm
1600 ppm
2)
0...2000 ppm
0...255 min
0...5000 m
Range
0...100%
20% = 2 V
0...100%
40% = 4 V
0...100%
60% = 6 V
0...100%
100% = 10 V
0...255 min
0...2
0...1
7: display only
Default
ON
3
0
ON
800 ppm
200 ppm
0 min
400 m
Default
120 min
0
0
Page 6-8