Vector TLC3-FCR-M-U-230 Series Install Sheet

Vector TLC3-FCR-M-U-230 Series Install Sheet

Programmable pid fan coil controller

Advertisement

Quick Links

Fan Coil Controller TLC3-FCR-M-U-230
TLC3-FCR-M-U-230, Programmable PID Fan Coil Controller
Features
Proven PID controls algorithm reduces room temperature fluctuations and energy consumption
Low power energy consumption: < 1W per unit
Relays switching for outputs each up to 300W
Temperature control for 2 or 4-pipe fan coil systems.
Automatic fan control for three stage fans.
Cost saving option with Economy functionality and set point limitations
Control for modulating heating, cooling and fan only operation modes
Deluxe Version:
Clock and time schedule functions with power failure clock protection
Blue backlight for LCD
Infrared remote controller option:
With special features for Boost and delayed switching on or off
Ordering
Item Name
Item code
Variant
Power
TLC3-FCR-M2-U-24
40-10 0141
24VAC/DC
TLC3-FCR-M2-U-120
40-10 0151
Standard
120VAC
TLC3-FCR-M2-U-230
40-10 0102
230VAC
TLC3-FCR-M2-U-D-24
40-10 0146
24VAC/DC
TLC3-FCR-M2-U-D-120
40-10 0156
Deluxe
120VAC
TLC3-FCR-M2-U-D-230
40-10 0103
230VAC
TLC3-FCR-M4-U-24
40-10 0142
24VAC/DC
TLC3-FCR-M4-U-120
40-10 0152
Standard
120VAC
TLC3-FCR-M4-U-230
40-10 0106
230VAC
TLC3-FCR-M4-U-D-24
40-10 0147
24VAC/DC
Deluxe
TLC3-FCR-M4-U-D-120
40-10 0157
120VAC
TLC3-FCR-M4-U-D-230
40-10 0107
230VAC
-W01
-1
Cooling only
Selection of fans
Do not directly connect devices that exceed 250 VAC, 2(1.2) A. Observe startup current on inductive loads!
Do not connect more than one fan coil unit to one controller.
Modulating Actuators:
Choose actuators with an input signal type of 0-10V DC or 2-10V DC. Observe maximal signal current of
1mA!
Mounting location
 Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of
average temperature.
 Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.
 Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
 Location of mounting is less critical if external temperature sensors are used.
Installation
1.
Connect the wires to be connected to the terminals of the power case according to wiring diagram
2.
Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding
screw is facing to the ground. Make sure the mounting screw heads do not stand out more than 5
mm (0.2") off the surface of the mounting plate.
3.
Slide the two latches located on the top of the front part into the hooks at the upper side of the
mounting plate.
4.
Carefully lower the front part until the interconnector reaches the mounting-plate. Continue
pressing in a gentle way until the front part is fully connected. While inserting the connectors, a
slight resistance can be felt. This is normal. Do not use excessive force!
5.
With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the
front part to the mounting plate. This screw is located on the front lower side of the unit. There is no
need to tighten the screw too much.
Power Failure
Upon power-interruption, all parameters and setpoints are memorized in non-volatile memory and therefore
do not have to be re-entered again.
Error messages
Err1:
Error temperature sensor. The internal temperature sensor may be damaged or not present.
FP:
Steady: Frost protection is active.
Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key.
Doc: 70-00-0180 V3.0 Date: 20110928
Display and Operation
Mode
Display of operation mode
Indicators
1 Remote temperature
sensor
Up :Increase setpoint
(Parameter setting: scroll
menu options and
parameters)
Features
Left (POWER): Press < 2 sec.: Toggle
Fan coil controller with:
Economy -Comfort mode or switch from
1 TI int, 1 external input
OFF to ON
3 DO (Relay) Fan control
Press > 2 sec.: Turn unit OFF. Text OFF
1AO (0-10VDC) PID valve control
displayed with current time (deluxe)
temperature (standard)
(Parameter setting: Return to previous
level. ESC)
1 TI int
Technical Specification
3 DO (Relay) Fan control
2AO (0-10VDC) PID valve control
Power Supply
Operating Voltage
Power Consumption
Electrical Connection
Add to name or code for special
Deluxe type only:Power backup for real time clock
settings
Temperature Inputs
Signal Inputs
Range
Accuracy
Digital Switching Outputs
Signal Outputs
Switching Type
AC Switching power
Insulation strength
between relays contacts and system electronics:
between neighboring relays contacts
Analog Outputs
Output Signal
Minimum impedance / maximum load
Operation
Climatic Conditions
Temperature
Humidity
Environment
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
Standards
Product standards
Automatic electrical controls for household and similar use
Special requirement on temperature dependent controls
Electromagnetic compatibility for
domestic sector
Degree of Protection
Pollution Class
Safety Class:
Overvoltage Category: for -24 types
RoHS
General
Dimensions (H x W x D) Front part:
Material:
Weight (including package)
Fan Coil Controller TLC3-FCR-M-U-230
Large Digits: Display of input
or parameter value.
Small Digits: Display of
setpoint, clock or parameter
number.
Vertical Bar: Fan speed or
proportional output
Right (OPTION)
Press < 2 sec.: Select fan speed:
Low, medium, high or auto
Press > 2 sec.: Manual H/C change
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Down: Decrease setpoint
(Parameter setting: scroll menu
options and parameters)
210 – 250 V AC 50/60 Hz
Max 1W, 1.5VA
Terminal Connectors
Min 48h if charged for 24h
RT Int., Ext. (Sxx-Tn10 sensor)
0...50 °C (32...122 °F)
0.5°C (1°F)
DO1 to DO3
Relays
0...250V AC 2A max. each output
3750V AC to EN 60 730-1
1250V AC to EN 60 730-1
AO1, For TLC3-FCR-M4 AO2
DC 0...10 V
10kOhm, ±1mA.
To IEC 721-3-3
class 3 K5
0°C ...50°C (32°F...122°F)
<95% R.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25°C...70°C (-13°F...158°F)
<95% R.H. non-condensing
class 2M2
conformity
EMC Directive
2004/108/EC
Low Voltage Directive
2006/95/EC
EN 60 730 –1
EN 60 730 – 2 - 9
Emissions: EN 60 730-1
Immunity: EN 60 730-1
IP30 to EN 60 529
II (EN 60 730-1)
for -24 types
III (IEC 60 536)
for -230 types
II (IEC 60 536)
I (EN 60 730-1)
for -230 types
III (EN 60 730-1)
Compliant
16 x 73 x 113mm (0,7 x 2.9 x 4.5 in.)
Power case:
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.)
Cover, back part
ABS plastic (UL94 class V-0)
Mounting Plate
Galvanized Steel
Standard:
295g (10.4oz)
Deluxe (-D):
305g (10.7oz)
© Vector Controls GmbH, Switzerland
Fan Coil Controller TLC3-FCR-M-U-230
Wiring Diagram
SGND
X
T EXT
230V AC
IN
2
6
7
L
M
X1
1
3
4
5
N
Y1
Y2
Y3
0V
Fan
Fan
Fan
Low
Med
High
SGND
AO2
230V AC
Cool
2
6
7
L
M
U2
1
3
4
5
Y1
Y2
Y3
N
0V
Fan
Fan
Fan
Low
Med
High
Description:
N
Power supply:
0V Neutral
L
Power supply:
230VAC
Y1
Binary output 230V AC:
Fan speed low
Y2
Binary output 230V AC:
Fan speed medium
Y3
Binary output 230V AC:
Fan speed high
TLC3-FCR-M2-U:
M
Signal common:
Common 0 potential for inputs and analog outputs.
NTC 10kΩ @ 25°C (77°F) or open contact to SGND
X1
External input:
0...10 V DC
U1
Analog output:
TLC3-FCR-M4-U:
M
Signal common:
Common 0 potential for inputs and analog outputs.
0...10 V DC
U2
Analog cooling output:
0...10 V DC
U1
Analog heating output:
Dimensions
73 (2.9)
32 (1.3)
Space required in flush mounting box:(H x W x D) 60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.)
Distance for mounting screws:Horizontal and vertical: 45 to 63mm (1.8 to 2.5 in.)
AO1
8
X
T INT
U1
TLC3-FCR-M2-U-230
AO1
Heat
8
X
T INT
U1
TLC3-FCR-M4-U-230
16 (0.7)
Subject to alteration

Advertisement

loading

Summary of Contents for Vector TLC3-FCR-M-U-230 Series

  • Page 1 Distance for mounting screws:Horizontal and vertical: 45 to 63mm (1.8 to 2.5 in.) Material: Cover, back part ABS plastic (UL94 class V-0) Mounting Plate Galvanized Steel Weight (including package) Standard: 295g (10.4oz) Deluxe (-D): 305g (10.7oz) Doc: 70-00-0180 V3.0 Date: 20110928 © Vector Controls GmbH, Switzerland Subject to alteration...