Remote Sensing Probes Type T17; Installation At Normal Pressure - E+E Elektronik HTS801 User Manual

Humidity and temperature sensor for high humidity and chemically polluted conditions
Table of Contents

Advertisement

Removing the probe
1.
Hold firmly the probe to avoid it being suddenly expulsed when releasing the lock. Do not bend damage the
probe cable.
2.
Loosen slowly the lock nut with a spanner (spanner width 24) only till the probe is pushed out by the
overpressure in the process. Do not completely loosen the lock nut, but only as much as necessary for the
probe to slide.
3.
After the probe has been pushed out of the process up to the stop, close the ball valve.
4.
Remove the probe from the ball valve.
NOTICE
Observe the correct positioning of the sealing element 1 before reinstalling the probe.
4.7
Remote Sensing Probes Type T17
RH
code "probe length"
T
code "cable length"
150 (5.9)
4.7.1.
Installation at Normal Pressure
HA010201
Fig. 32
Mounting of sensing probe with flange (accessory)
A.mounting.flange.12.mm.(1/2").for.the.humidity.probe.and.a.mounting.flange.6.mm.(1/4").for.the.temperature.
probe are available as an accessory. The immersion depth is adjustable.
Order codes:
Flange
1)
code "cable length"
1)
1/2".ISO.or.1/2".NPT
Optional cut-in fitting
see accessories datasheet
1)
1/2".ISO.or.1/2".NPT
Optional cut-in fitting
see accessories datasheet
RH probe
RH probe (12 mm (1/2"))
HA010201
HA010207
T probe
T probe (6 mm (1/4"))
HA010207
Humidity and Temperature Sensor for High Humidity and Chemically Polluted Conditions | 31