E+E Elektronik CDS201 Quick Manual

Room sensors with rs485 interface
Hide thumbs Also See for CDS201:

Advertisement

Quick Links

Quick Guide
CDS201 | HTS201 | TES201
Room Sensors with RS485 Interface
PLEASE NOTE
Find these documents and further product information on the product sites at
www.epluse.com/cds201 www.epluse.com/hts201
Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property.
For correct cabling of the device, always observe the presented wiring diagram for the product version used.
The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling,
installation, wiring, power supply and maintenance of the device.
Address Setting
DIP switch
1
0
0 0 0 0 0
0 0
0
DIP switch
1
0
1 1 0 1 0
0 0
0
BACnet Setup
BACnet PICS are available for download at the according product website.
Baud rate
Data bits
Parity
Stop bits
BACnet address
The PICS (Product Implementation Conformance Statement) is available for download at the according product website.
The recommended settings for multiple devices in a BACnet MS/TP network are 38 400, 8, none, 1.
The communication parameters can be set via:
PCS10 Product Configuration Software and the the appropriate configuration cable HA011018.
The PCS10 can be downloaded free of charge from www.epluse.com/pcs10.
BACnet protocol, see the PICS.
www.epluse.com/tes201.
Pin number
Address setting via PCS10 Product Configuration Software:
All DIP switches at position 0
(factory setting: 45).
Example: Address is set via configuration software.
Modbus address setting via DIP switch:
Setting the DIP switch to any other address than 0 overwrites the address selected via
configuration software.
Example: Address set to 11 (=00001011 binary).
Factory settings
acc. to ordering code
8
None
1
45
Function
V+ supply voltage
1
24 VAC ±15%, 15 - 35 V DC class III
Max. 30 V DC class 2 (North America)
2
GND
3
RS485 A (D+)
4
RS485 B (D-)
5
V+ supply voltage
6
GND
7
RS485 A (D+)
8
RS485 B (D-)
address has to be set via configuration software
User selectable values (via PCS10)
9 600, 19 200, 38 400, 57 600, 76 800, 115 200
8
None
1
0...127
(Europe)

Advertisement

loading

Summary of Contents for E+E Elektronik CDS201

  • Page 1 Quick Guide CDS201 | HTS201 | TES201 Room Sensors with RS485 Interface PLEASE NOTE Find these documents and further product information on the product sites at www.epluse.com/cds201 www.epluse.com/hts201 www.epluse.com/tes201. Electrical Connection WARNING Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property.