HTTP-Webserver: Port 80
For a quick communication check, enter the desired IP address in a web browser and connect with the
HTS801 Ethernet module's Webserver.
Fig. 23
E+E net web interface screenshots
Alternatively, send an ICMP echo request ("ping") to check correct communication settings.
IPv4 Settings
IP Address
Subnet Mask
Gateway
DNS
Tab. 3
IPV4 settings
DHCP options can be set with jumper on the electronics board, refer to Fig. 24. Factory setting: DHCP disabled
(static IP).
Fig. 24
Ethernet module - DHCP setting
The setup of the Modbus TCP communication can be performed via PCS10 Product Configuration Software or via
display and push-buttons, see chapter 11.3 Optional Menus Fig. 57 IP settings.
Modifying the IP address via PCS10 or display is possible only when the DHCP jumper is set to "Static".
Otherwise the IP settings are read-only.
Factory settings
192.168.0.64
255.255.255.0
192.168.0.1
192.168.0.1