Unigas N880X Manual page 88

Table of Contents

Advertisement

Available languages

Available languages

Termi- nal
group
Connection symbol
X10-01
X10-02
X10-03
X50
X51
Description of connection termi- nals
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal transformer
PIN2
x
AC power signal GO
PIN1
x
AC power signal fan motor (G)
QRI... (IR detector) / QRA7... signal
voltage
PIN6
x
PIN5
x
Protective earth (PE)
PIN4
x
Neutral conductor (N)
PIN3
x
Power signal
QRI... (IR detector) / QRA7... power
supply
PIN2
x
PIN1
x
QRB... signal voltage
Ionization probe (ION) (alternati- vely
QRA2.../ QRA4.U/QRA10..., refer to
section Description of inputs and out-
PIN1
x
puts)
PIN6
x
Reference ground (PELV)
PIN5
x
Communication signal (CANL)
PIN4
x
Communication signal (CANH)
AC power supply for actuators / display
and operating unit AZL5...
PIN3
x
AC power supply for actuators / display
and operating unit AZL5...
PIN2
x
Shield connec-
tion
PIN1
x
PIN6
x
Reference ground (PELV)
PIN5
x
Communication signal (CANL)
PIN4
x
Communication signal (CANH)
AC power supply for actuators / display
and operating unit AZL5...
PIN3
x
AC power supply for actuators / display
and operating unit AZL5...
PIN2
x
Shield connec-
tion
PIN1
x
Electrical rating
AC 230 V +10 % / -15 %, 50...60 Hz,
max 1 mA
AC 12 V +10 % / -15 %, 50...60 Hz,
max 1.2 mA
Umax DC 5 V
AC 230 V +10 % / -15 %, 50...60 Hz,
Imax 500 mA
DC 14 / 21 VC Imax 100 mA
Max. DC 8 V
Umax (X3-04-PINS) Imax. 0.5 mA
DC U <5 V, Rw = 120 Ù, level to ISO-DIS
11898
AC 12 V +10 % / -15 %, 50...60 Hz,
Fuse max. 4 A
(functional earth)
DC U <5 V, Rw = 120 Ù, level to ISO-DIS
11898
AC 12 V +10 % / -15 %, 50...60 Hz,
Fuse max. 4 A
(functional earth)

Advertisement