10.2 Address and activate the AUX3 servomotor.
Usually these operations are already set in the manufacturer factory.
They would be necessary in same cases as: the substitution of the servomotor, in case the FGR mode were not activated yet or the LMV5x were be
supplied loose...
WARNING: for LMV52.400 device, in case of FGR servomotor addressing: the only possible choice is AuxActuator3. Don't set
the FGR servomotor for a different one.
1st level
2nd level
Params & Display
Actuators
After the addressing, activate the FGR servomotor.
1st level
2nd level
Params & Display
RatioControl
3rd level
4th level
Addressing
AirActuator
GasActuat
OilActuat
AuxActuator
AuxActuator 2
AuxActuator 3
3rd level
4th level
GasSettings
OilSettings
AuxActuator
AirActuator
AuxActuator 1
AuxActuator 2
AuxActuator 3
VSD
GasActuator
OilActuator
5th level
6th level
AuxActuator 3
5th level
6th level
deactivated
Deactivated for LMV52.xxx
damper act
VSD active
AUX3
AUX3 for LMV51.300
VSD+Aux3
deactivated
activated
activated
air influen
Activated for LMV52.xxx
Activated
Activated
31
Description
Parameter settings for fuel/ air ratio
control
Parameter settings for firing on Gas
or on Oil
AuxActuator 3 MUST be chosen
Description
Parameter settings for fuel/ air ratio
control
Parameter settings for firing on Gas
or on Oil
Deactivated for LMV52.xxx
AUX3 for LMV51.300
Choice according to the Operation
mode gas setting or oil setting.