Environmental

Shock and Vibration

1
When operated in temperatures below 0 °C, you must use the PS-5 power supply, or another power supply rated for below 0 °C.
NI cDAQ-9172 User Guide and Specifications
The NI cDAQ-9172 chassis is intended for indoor use only. For outdoor
use, mount the system in a suitably rated enclosure.
Operating temperature
(IEC-60068-2-1 and IEC-60068-2-2) .....–20 to 55 °C
Storage temperature
(IEC-60068-2-1 and IEC-60068-2-2) .....–40 to 85 °C
Ingress protection ...................................IP 30
Operating humidity
(IEC-60068-2-56) ...................................10 to 90% RH, noncondensing
Storage humidity
(IEC-60068-2-56) ...................................5 to 95% RH, noncondensing
Maximum altitude...................................2,000 m
Pollution Degree (IEC 60664) ................2
To meet these specifications, you must panel mount the NI cDAQ-9172
system and affix ferrules to the ends of the terminal lines.
Operational shock ...................................30 g peak, half-sine, 11 ms pulse
Random vibration
Operating .........................................5 to 500 Hz, 0.3 g
Nonoperating ...................................5 to 500 Hz, 2.4 g
1
(Tested in accordance with
IEC-60068-2-27. Test profile
developed in accordance with
MIL-PRF-28800F.)
(Tested in accordance
with IEC-60068-2-64.
Nonoperating test profile
exceeds the requirements of
MIL-PRF-28800F, Class 3.)
82
rms
rms
ni.com