Mounting location

Mount this sensor...
Space RH sensor
Duct RH sensor
Outdoor RH sensor
Carrier Sensors
In this location
On an interior wall
Approximately 5 feet (1.5 meters) from the floor, beside the space
temperature sensor
At least 4 feet (1.2 meters) from any corner. Reduced airflow in corners
results in erratic sensor readings.
Vertically so that the Carrier logo is correctly oriented
Do not mount the sensor:
In drafty areas such as near heating or air-conditioning ducts, open windows,
or fans
Over heat sources such as baseboard heaters, radiators, or wall-mounted
light dimmers
In areas of excessive moisture, corrosive fumes, or vibration
Sensors mounted in these areas will produce inaccurate readings.
NOTE The sensor mounting plate accommodates the NEMA standard 4x2-in.
electrical box. However, the sensor can be mounted directly on the wall surface if
local codes permit.