Mounting location

Mount the sensor:
In an area representing the average temperature in the space
On an interior wall
Approximately 5 feet (1.5 meters) from the floor, or as required by local code
At least 4 feet (1.2 meters) from any corner
At least 2 feet (.6 meter) from an open doorway
Do not mount the sensor:
In drafty locations such as near air conditioning or heating ducts, or near open windows
Over heat sources such as baseboard heaters, radiators, directly above wall-mounted lighting dimmers,
or in direct sunlight
NOTE The sensor mounting plate accommodates the NEMA standard 4x2-in. electrical box. However, the
sensor can be mounted directly on the wall surface if local codes permit.

To wire and mount the sensor

Turn the 2 setscrews at the bottom of the sensor clockwise to release the sensor's cover from the
1
mounting plate.
Lift the cover from the bottom, and then release it from the top fasteners.
2
Feed the wires from the electrical box through the opening in the center of the sensor mounting plate.
3
Use the 2 mounting screws provided to attach the mounting plate to the electrical box.
4
Strip the outer jacket from the cable for at least 3 inches (7.62 cm). Strip .25 inch (.6 cm) of insulation
5
from each wire. Cut the shield and drain wire from the cable.
Use the appropriate diagram below to connect the wiring to the sensor's terminals.
6
Reattach the sensor's cover to the mounting plate, inserting the top first.
7
Turn the two Allen screws counterclockwise to secure the cover to the mounting plate.
8
Wire the sensor to the Open controller. See the controller's Installation and Startup Guide for details.
9
NOTE Clean sensor with damp cloth only. Do not use solvents.