INSTRUCTIONS Dual Spectrum ® Infrared Flame Detector PM-5MPX IMPORTANT Be sure to read and understand the entire instruction manual before installing or operating the Model PM-5MPX Detector. Only qualified personnel should install, maintain or operate the flame detection system. CAUTION If this equipment is used in a manner not specified in this manual, safety protection may be impaired.
4 x 0.203 Figure 1—Dimensions of PM-5MPX in Inches APPLICATIONS OPERATING VOLTAGE— 9 to 30 Vdc at the detector (observe polarity), including The PM-5MPX is intended for fast detection of line drops and ripple. hydrocarbon fueled fires in harsh chemical environments. The detector is ideal for semiconductor wet benches and NOTE is suitable for clean-rooms, gas cabinets, and other...
Table 1—PM-5MPX Wiring Harness Identification 100% Wire Color Description Black Power Return Brown Power Return V+, Input Power Orange V+, Input Power Yellow Alarm + Green Alarm + Blue Alarm – A2004 Violet Alarm – Figure 2—Graphical Representation of Detector Range as a Gray Trouble + Function of Angle from the Optical Axis...
FALSE ALARM IMMUNITY The number of detectors required to protect a given area will depend on the size of the area, the distance from the The PM-5MPX is highly resistant to false alarms. However, detector and the size and type of the fire threat. Certain a fire alarm output due to non-fire stimuli is possible.
INTRINSICALLY SAFE CIRCUITS SYSTEM TEST Intrinsically safe installations require the use of suitable After the fire protection system is installed, it should be and approved barriers, an approved fire alarm control tested for correct operation. The detectors may be tested panel that is compatible with the barriers, and wiring with live fires or by using the hand-held model PSS-MP methods consistent with ANSI/ISA-RP12.6 and other...
MAINTENANCE 3. Interconnection Wiring. Correct interconnection wiring should be checked by disconnecting any wire from the multi-conductor cable were it is connected ROUTINE VISUAL INSPECTION to the power or alarm circuit. The result, in an A properly installed PM-5MPX detector system is highly approved wiring scheme, should be a trouble signal resistant to blinding by contamination build-up on the indication at the control panel.
ORDERING INFORMATION WARNING A full system test results in an alarm output. This When ordering, please specify: will result in the suppression system being activated if it is not disabled prior to testing. PM-5MPX Dual Spectrum ® Infrared Flame Detector DEVICE REPAIR AND RETURN For assistance in ordering a system to meet the needs of a specific application, contact:...
APPENDIX A FM APPROVAL DESCRIPTION AND PERFORMANCE REPORT HAZARDOUS LOCATION RATINGS • Intrinsically safe for Class I, II, III, Div. 1, Groups C, D, E, F and G Hazardous (Classified) Locations per FM 3610. • Non-incendive for Class I, Div. 2, Groups A, B, C and D Hazardous (Classified) Locations per FM 3611. AUTOMATIC FIRE ALARM SIGNALING PERFORMANCE (FM 3620: 2000) RESPONSE CHARACTERISTICS (Typical Response Time <...
Page 11
FM Approval Description and Performance Report – Continued FALSE ALARM IMMUNITY COMBINED WITH FIRE SOURCE False Alarm Fire Source False Alarm Source Source Distance Fire Source Distance (feet) (inches) Arc welding, unmodulated 10 in propane Arc welding, modulated 10 in propane 70 W sodium vapor lamp, unmodulated 10 in propane 70 W sodium vapor lamp, modulated...
Page 17
Det-Tronics manufacturing system is certified to ISO 9001— Corporate Office Phone: +1 952 .941 .6665 the world’s most recognized quality management standard . 6901 West 110 Street Toll-free: +1 800 .765 .3473 Minneapolis, MN 55438 USA Fax: 952 .829 .8750 www.det-tronics.com det-tronics@carrier .com...