Primary Air Temperature sensor

Primary Air Temperature sensor
Part #33ZCSENPAT
The Primary Air Temperature (PAT) sensor monitors the supply air temperature. Use a PAT sensor if state or
local code requires the use of conduit. If conduit is not required, you can use an SAT sensor.

PAT sensor specifications

Operating range
Sensor tolerance
Physical
26
6 in.
(15.2 cm)
probe
-40° to 245°F (-40° to 118°C) with a nominal resistance of 10,000 ohms at
77°F (25°C). See table below.
Accuracy of ±0.36°F (0.2°C) from 0° to 70°C
Has a thermistor encased with a 6-inch (15.2-cm) stainless steel probe. Has a
4x2-inch electrical box. Includes 2 mounting screws.
4 x 2 in.
(10.2 x 5.1 cm)
electrical box