PRODUCT DESCRIPTION

The ICT180S-12I Intelligent Distribution Panel is designed for either 12 or 24VDC applications. It
provides 12 output positions that are individually protected by blade type fuses. Nine of the outputs
use ATO/ATC blade fuses that are rated up to 25A each. Three of the outputs use JCASE fuses and are
rated up to 40A each. These fuses are located on the front of the panel for easy monitoring and
replacement. Each positive output terminal point is connected through a fuse to a positive internal bus.
All negative output terminal points are connected to a negative internal bus.
There are five alarm inputs on the back of the panel for connecting external Dry Contact sensors for
site monitoring and reporting of alarms such as door, water, and smoke detectors.
System voltage, system current, output currents, fuse status, and alarm input status can be monitored
onsite through the LCD graphics display. Fuse status is also displayed by an LED indicator located over
each fuse. Form "C" alarm contacts (C/NO/NC) are provided on the back of the panel which can be
connected to an external alarm circuit for monitoring alarms generated by the panel.
Remote monitoring is available through the integrated security protected Ethernet communications
port on the back of the panel. The panel has a built-in web server with an embedded web-based GUI
that can be accessed using any standard commercial web browser such as Internet Explorer. The web
server not only displays panel information, it can also be set up to send an alarm to user-defined
email accounts in the event a fault occurs. The web server can also be used for data logging of up to
30 days of time stamped event information. All these features are packaged in a 1RU enclosure to
save valuable rack space and fit standard 19" equipment racks. The rack mounting position is
adjustable.
FRONT PANEL
1. FUSE STATUS LEDs: Turns on when a fuse is blown or missing.
2. ATO/ATC FUSES: Location of the ATO/ATC fuses rated up to 25A.
3. LCD: Displays system voltage, system current, output current and fuse
status for each of the 12 output positions.
4. OUTPUT SELECT BUTTON: For switching between LCD screens, and resetting
network, web server and password settings to original factory default values.
5. JCASE FUSES: Location of the JCASE fuses rated up to 40A.