BMS Protect TemHigh
BMS Protect TemLow
Remark
If your inverter's information panel is not displaying a Fault light, check the following list to make sure
that the present state of the
installation allows proper operation of the unit.
·Is the inverter located in a clean, dry, and adequately ventilated place?
·Have the DC input breakers been opened?
·Are the cables adequately sized and short enough?
·Are the input and output connections and wiring in good condition?
·Are the configurations settings correct for your particular installation?
·Are the display panel and the communications cable properly connected and undamaged?
Contact GS ESS Power Customer Service for further assistance. Please be prepared to describe
details of your system installation and provide the model and serial number of the unit.

7.2 Maintenance

Inverters generally do not need any daily or routine maintenance. Heat sink should not be blocked
by dust, dirt or any other items. Before the cleaning, make sure that the DC SWITCH is turned OFF
and the circuit breaker between inverter and electrical grid is turned OFF. Wait at least for 5 minutes
before the Cleaning.
During the process of using the inverter,the manage person shall examine and maintain the machine
regularly.The concrete operations are follow.
1: Check that if the cooling fins on the rear of house are covered by dirts, and the machine should be
cleaned and absorbed dust when necessary.This work shall be check time to time.
2: Check that if the indicators of the inverter are in normal state,check if the keys of the inverter are in
normal state,check if the display of the inverter is normal.This check should be performed at least every
6 months.
3: Check that if the input and output wires are damaged or aged.This check should be performed
at least every 6 months.
4: You should keep the inverter panels clean and their security checked at least every 6 months.
· Inverter cleaning
Please clean the inverter with an air blower, a dry & soft cloth or a soft bristlebrush. Do NOT clean
the inverter with water,corrosive chemicals, detergent, etc.
· Heat sink cleaning
For the long-term proper operation of inverters, ensure there is enough space around the heat
sink for ventilation, check the heat sink for blockage (dust, snow, etc.) and clean them ifthey exist.
Please clean the heat sink with an air blower, a dry & softcloth or a soft bristle brush. DoNOT clean
the heat sink with water, corrosive chemicals, detergent, etc.
Battery temperature is high
· Wait for 5 minutes, check again.
· Or seek help from us, if not go back to normal state.
Battery temperature is low
· Wait for 5 minutes, check again.
· Or seek help from us, if not go back to normal state