Specifications

This section provides the physical and environmental specifications of the
enclosure.
Physical specifications
Environmental specifications

Parts list

The enclosure is a Tier 1 customer replaceable unit (CRU). Replacement of Tier 1
CRUs is your responsibility. If IBM installs a Tier 1 CRU at your request, you will be
charged for the installation.
For more information about the terms of the warranty and getting service and
assistance, see Appendix A, "IBM Statement of Limited Warranty Z125-4753-10
08/2008," on page 21.
If you are instructed to return a component, follow all packaging instructions, and
use any packaging materials for shipping that are supplied to you.
Size and weight
Width: 42.8 cm (16.85 in.)
Depth: 50.8 cm (20 in.)
Height: 4.3 cm (1.75 in.)
Weight: 7.0 kg (15.5 lb)
Specification
Operating
Ambient
10° to 32°C
temperature range
(50° to 89°F)
Temperature
1°C per minute;
variation (thermal
maximum 10°C per
gradient)
hour
(2°F per minute;
maximum 18°F per
hour)
Relative humidity
20% to 80%;
(humidity gradient)
non-condensing 10%
per hour
Wet bulb
26°C (79°F) maximum 29°C (84°F) maximum 29°C (84°F) maximum
Altitude
-304.9 m to 9 144 m
(-1000 ft to 30 000 ft)
Electrical
Input frequency: 47 to 63 Hz
Power: 135 W (maximum)
Input voltage: 100 to 240 V ac
Output rating:
14 A at +5 V dc
v
6 A at +12 V dc
v
Storage or
non-operating
Transportation
-40° to 60°C
-20° to 60°C
(-40° to 140°F)
(-4° to 140°F)
1°C per minute;
1°C per minute;
maximum 20°C per
maximum 20°C per
hour
hour
(1°F per minute;
(2°F per minute;
maximum 36°F per
maximum 36°F per
hour)
hour)
10% to 80%;
10% to 80%;
non-condensing 10%
non-condensing 10%
per hour
per hour
-304.8 m to 9 144 m
-304.8 m to 9 144 m
(-1000 ft to 30 000 ft)
(-1000 ft to 30 000 ft)