Advertisement
The N322 is a 2-output digital electronic controller for heating and cooling applications. It is available with NTC thermistor input sensor, Pt100, Pt1000 or J/K/T type thermocouple. Sensor offset correction is provided. The 2 independent outputs can be used as control or alarm. The features of a particular model (input sensor type, sensor range, mains supply, etc.) are identified by the label placed on the controller body.
INPUT SENSOR: The sensor is chosen by the user at the time of purchase and is presented on the upper side of the equipment box. The options are:
WARM-UP: 5 minutes
MEASUREMENT RESOLUTION:
From –19.9 to 199.9 º with NTC, Pt100 and Pt1000: 0.1
Elsewhere: 1
Note: The equipment keeps its precision all over the range, despite the lack of display resolution in a part of the range does not allow its visualization.
OUTPUT1: Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A Resistive)
OUTPUT2: Relay: 3 A / 250 Vac, SPST
POWER SUPPLY:
100~240 Vac (± 10%) or 24 Vdc/ac (12~30 Vdc/ac)
Mains frequency: 50~60 Hz. Power consumption: 5 VA
check the power supply specification before energizing the controller.
DIMENSIONS:
Width x Height x Depth: 74 x 32 x 75 mm
Panel cut-out: 70 x 29 mm; Weight: 100 g
ENVIRONMENT:
Operating temperature: 0 to 40°C (32 to 104°F)
Storage temperature: -20 to 60°C (-4 to 140°F)
Relative humidity: 20 to 85% non-condensing
CASE:
Polycarbonate UL94 V-2; Protection: Front panel: IP65, Box: IP42
Suitable wiring: Up to 4.0 mm²
RS-485 digital communication; RTU MODBUS protocol (optional)
Serial interface not isolated from input circuitry.
Serial interface isolated from input circuitry, except in 24 V powered model.
It is important to follow the recommendations below:
BACK PANEL
Fig. 1 below shows the controller connections to sensor, mains and outputs.
Fig. 1 – N322 terminals
Pt100 with 3 conductors: Terminals 11, 12 and 13 must have the same wire resistance for proper cable length compensation. For 2 wire Pt100, short circuit terminals 11 and 13.
The controller requires the internal parameters to be configured according to the intended use for the instrument. The parameters are organized in 4 groups or levels:
Level | Function |
0 | Temperature measurement |
1 | Setpoint Adjustment |
2 | Configuration |
3 | Calibration |
Upon power-up, the N322 display shows for 1 second its firmware version. This information is useful when consulting the factory.
Then, the temperature measured by the sensor is shown on the display. This is the parameter level 0 (temperature measurement level).
To access level 1, press for 1 second until the "
" message shows up. Pressing
again, the "
" parameter is presented. To go back to level 0, press
once more.
To access level 2 of parameters, press for 2 seconds until the "
" message is shown. Release the
key to remain in this level. Each new pressing on the
key will advance to the next parameter in the level. At the end of the level, the controller returns to the first level (0). Use the
and
keys to alter a parameter value.
Notes:
In this level only the Setpoint ( and
) parameters are available, alternating the names with their respective values. Adjust the desired temperature for each setpoint clicking on the
and
keys.
![]() Set Point 1 | Temperature adjustment for control OUTPUT 1. ![]() ![]() ![]() |
![]() Set Point 2 | Temperature adjustment for control OUTPUT 2. ![]() ![]() ![]() |
Contains the configuration parameters to be defined by the user, according to the system's requirements. Use and
keys to set the value. The display alternates the parameter name and respective value.
![]() | Temperature Unit - Selects display indication for degrees Celsius or Fahrenheit.![]() ![]() | ||
![]() | Input Type - Selects the input sensor type to be connected to the controller. Available only for thermocouple models, allowing selection of types J, K and T.
| ||
![]() | Sensor Offset - Offset value to be added to the measured temperature to compensate sensor error. | ||
![]() | SP Low Limit - Lower range for SP1 and SP2. SPL must be programmed with a lower value than spK. | ||
![]() | SP High Limit - Upper range for SP1 and SP2. SPx must be greater than spl. | ||
![]() | OUTPUT 1 Hysteresis: defines the differential range between the temperature value at which the OUTPUT 1 is turned on and the value at which it is turned off. In degrees. | ||
![]() | OUTPUT 2 Hysteresis: defines the differential range between the temperature value at which the OUTPUT 2 is turned on and the value at which it is turned off. In degrees. | ||
![]() | Control action for OUTPUT 1:![]() ![]() | ||
![]() | Action 2 - Control OUTPUT 2 action or Alarm functions:
The section Working with the Controller describes how these functions work. | ||
![]() Control | Control - Associates Setpoints and Outputs. ![]() ![]() | ||
![]() Off time 1 | Off time 1 - Defines the minimum off time for control OUTPUT 1. Once OUTPUT 1 is turned off, it remains so for at least the time programmed in ![]() ![]() Value in seconds, 0 to 999 s. | ||
![]() on time 1 | On time 1 - Defines the minimum on time for control OUTPUT 1. Once turned on, OUTPUT 1 remains so for at least the time programmed in ![]() ![]() Value in seconds, 0 to 999 s. | ||
![]() Delay 1 | Delay 1 - Delay time to start control. Upon power-on, control OUTPUT 1 is kept off until the time programmed in ![]() | ||
![]() Off time 2 | Off time 2 - Defines the minimum off time for control OUTPUT 2. Once OUTPUT 2 is turned off, it remains so for at least the time programmed in ![]() ![]() Value in seconds, 0 to 999 s. | ||
![]() on time 2 | On time 2 - Defines the minimum on time for control OUTPUT 2. Once turned on, OUTPUT 2 remains so for at least the time programmed in ![]() ![]() | ||
![]() Delay 2 | Delay 2 - Delay time for OUTPUT 2 to turn on relative to OUTPUT 1. This parameter defines a particular working mode, typically used in multiple stage systems, where OUTPUT 2 is allowed to go on only if OUTPUT 1 is already on for at least ![]() ![]() ![]() | ||
![]() Address | Address - Controllers with the optional RS485 Modbus RTU communication interface have the ![]() |
The controller is factory calibrated. The following parameters should be accessed only by experienced personnel. To enter this cycle, the key must be kept pressed for 4 seconds.
Don't press the and
keys if you are not sure of the calibration procedures. Just press the
key a few times until the temperature measurement level is reached again.
![]() | Password - Enter the correct password to unlock write operations for the parameters in the following levels. | |||
![]() | Calibration low - Offset value of the input. It adjusts the lower measurement range of the sensor. | |||
![]() | Calibration High - Gain calibration. It adjusts the upper measurement range of the sensor. | |||
![]() | Cold Junction Offset calibration - This parameter is available only for thermocouple. | |||
![]() | Factory Calibration - Restores factory calibration parameters. Change from 0 to 1 restores the calibration parameters with factory values. | |||
![]() | Protection - Defines the levels of parameters that will be password protected. See "Configuration Protection" for details. | |||
![]() | Password Change - Allows changing the current password to a new one. Values from 1 to 999 are allowed. | |||
![]() | Serial number - First part of the controller electronic serial number. | |||
![]() | Serial number - Second part of the controller electronic serial number. | |||
![]() | Serial number - Third part of the controller electronic serial number. |
Multiple output controllers are suited for controlling multiple stage systems.
Other applications require OUTPUT 1 to be the control output and OUTPUT 2 to be the alarm.
There are eight distinct alarm functions implemented in OUTPUT 2, selected by the parameter , described below:
- Low temperature alarm – OUTPUT 2 is turned on when the measured temperature falls below the
value.
- High temperature alarm – OUTPUT 2 is turned on when the measured temperature exceeds the value programmed in
.
- Inside range alarm – OUTPUT 2 is turned on when the measured temperature is within the range defined by:
and
- Outside range alarm: OUTPUT 2 is turned on when the temperature falls outside the range defined by:
and
Functions are identical to the above ones except that they incorporate the Initial Blocking feature, which inhibits the output if an alarm condition is present at start-up. The alarm will be unblocked after the process reaches a non-alarm condition for the first time.
In a multiple stage application, and
are configured to operate at different temperatures, creating a progressive sequence for turning on the outputs (compressors) in response to a system demand. The output delays for turning on the compressors (
and
) cause the compressors to be turned on one by one, minimizing energy demand.
Another usage for multiple output controllers is in systems that require automatic selection between cool and heat action. In these applications, one output is configured as reverse action (heating) and the other as direct action (refrigeration). The output status led P1 and P2 in the controller panel, signals when the control output in on.
A protection system to avoid unwanted changes to the controller parameters is implemented. The level of protection can be selected from partial to full. The following parameters are part of the protection system:
![]() | When this parameter is presented, the correct password should be entered to allow changes of parameters in the following levels. |
![]() | Defines the level of parameters that will be password protected:
|
![]() | Parameter for definition of a new password. Since it is located in the calibration level, can only be changed by a user that knows the current password. Valid passwords are in the range 1 to 999. |
Configuration protection usage
parameter is displayed before entering a protected level. If the correct password is entered, parameters in all following levels can be changed. If wrong or no password is entered, parameters in the following levels will be read only.
The master password allows user to define a new password for the controller, even if the current password is unknown. The master password is based in the serial number of the controller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]
For example the master password for the device with serial number 987123465 is:
1 9 3 6 as follows: 1 + = 987;
= 123;
= 465 = 1 + 9 + 3 + 6
How to use the master password:
Sensor measurement errors force the controller outputs to be turned off. The cause for these errors may have origin in a bad connection, sensor defect (cable or element) or system temperature outside the sensor working range. The display signs related to measurement errors are shown below:
![]() | Measured temperature exceeded maximum allowed range for the sensor. Broken Pt100, Pt1000 or T/C. Short circuited NTC sensor. |
![]() | Measured temperature is below minimum measurement range of the sensor. Short circuited Pt100, Pt1000 or T/C. Broken NTC. |
Warranty conditions are available on our website www.novusautomation.com/warranty.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the N322 and is the answer not in the manual?
Questions and answers