Installation
50/60 Hz earth (ground) loops
With very long control cables, earth loops (ground loops)
may occur. To eliminate earth (ground) loops, connect one
end of the screen-to-earth (ground) with a 100 nF
capacitor (keeping leads short).
2
2
Illustration 2.26
Avoid EMC noise on serial communication
This terminal is connected to earth (ground) via an internal
RC link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is shown
below:
Illustration 2.27
1
Min. 16 mm
2
Equalizing cable
Table 2.9
Alternatively, the connection to terminal 61 can be
omitted:
Illustration 2.28
1
Min. 16 mm
2
Equalizing cable
Table 2.10
28
VLT
Operating Instructions
PLC
FC
PE
PE
100nF
FC
FC
69
69
68
68
61
61
PE
PE
PE
PE
1
2
2
FC
FC
69
68
68
69
PE
PE
PE
PE
1
2
2
MG21A202 - VLT
®
AQUA Drive D-Frame

2.5.4 Control Terminal Types

Terminal functions and default settings are summarized in
2.5.6 Control Terminal Functions.
Illustration 2.29 Control Terminal Locations
Connector 1 provides four programmable digital
input terminals, two additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and
commons for the inputs and output
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
Some options available for ordering with the unit
may provide additional terminals. See the manual
provided with the equipment option
®
is a registered Danfoss trademark