Specifications
Digital output
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
1)
Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
1)
on 1-2 (NO) (Resistive load)
1)
on 1-2 (NO) (Inductive load @ cosφ 0.4)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 1-2 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 1-2 (NO) (Inductive load)
Max. terminal load (AC-1)
1)
on 1-3 (NC) (Resistive load)
1)
on 1-3 (NC) (Inductive load @ cosφ 0.4)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 1-3 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
on 1-3 (NC) (Inductive load)
Min. terminal load on 1-3 (NC), 1-2 (NO)
Environment according to EN 60664-1
Relay 02 Terminal number
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 4-5 (NO) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-5 (NO) (Inductive load)
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
Max. terminal load (AC-15)
1)
Max. terminal load (DC-1)
on 4-6 (NC) (Resistive load)
1)
Max. terminal load (DC-13)
on 4-6 (NC) (Inductive load)
Min. terminal load on 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1)
IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300 V AC 2 A
Control card, 10 V DC output
Terminal number
Output voltage
Max. load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
VLT
®
AQUA Drive D-Frame
Operating Instructions
2)3)
2)3)
®
MG21A202 - VLT
is a registered Danfoss trademark
Max. error: 0.1 % of full scale
1-3 (break), 1-2 (make)
400 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24V AC 2 mA
overvoltage category III/pollution degree 2
4-6 (break), 4-5 (make)
400 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
240 V AC, 2 A
240 V AC, 0.2 A
24 V DC, 0.1 A
24 V DC 10 mA, 24V AC 2 mA
overvoltage category III/pollution degree 2
2
1)
27, 29
0-24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
12 bit
12, 13
200 mA
2
80 V DC, 2 A
50 V DC, 2 A
10
10
80 V DC, 2 A
50 V DC, 2 A
50
10.5 V ±0.5 V
25 mA
75