Mitsubishi Electric TRANE TE-50A Instruction Book page 69

Air conditioning control system
Hide thumbs Also See for TRANE TE-50A:
Table of Contents

Advertisement

(3) Enter [255.255.255.0] in the [Subnet Mask] field (only when the IP address is [192.168.1.*]).
Note: If [255.255.255.0] is entered, set the IP addresses of all TE-50 units to [192.168.1.*].
(4) When monitoring the system remotely or using e-mail function via a dial-up router, enter the router IP
address in the [Gateway] field.
Leave the [Gateway] field blank when not connecting a dial-up router.
[192.168.1.254] is recommended for use as the IP address of the dial-up router. Refer to the dial-up router
instruction manual for details of how to set the IP address.
Note: [192.168.1.254] is recommended for use as the IP address of the dial-up router. Refer to the dial-up router
instruction manual for details of how to set the IP address.
Note: The use of a dial-up router with no modem requires a modem (for analog or ISDN) to be connected between the
router and the public phone line.
Settings for when connecting one or more TE-50/TW-50 controllers
(1) Select [1], [2], [3], or [4] in the [Controller] section to make settings for each TE-50/TW-50.
(2) Enter the IP address of the TE-50/TW-50 that is connected to the TE-200 in the [Dstn IP address] field.
A message that indicates that the connection information of the TE-50/TW-50 is being collected will appear
for a few minutes.
Note: TE-50/TW-50 will not operate properly and the TE-50/TW-50 software version will not appear if the entered address
does not match the ones that have been set on the TE-50/TW-50.
(2) LAN1 settings for connecting the TE-200/TE-50 to an existing LAN
(1) When connecting the TE-200/TE-50 to an existing LAN, consult the system administrator to decide the IP
addresses, subnet mask, and gateway addresses.
[2] LAN2 Settings
LAN2 is used only for BACnet
For how to make BACnet
Note: IP addresses of LAN1 and LAN2 must not duplicate.
[3] M-NET Settings
Note: Make the M-NET settings only on the TE-200.
(1) Switch the [Controller] setting between [AE200] and [Exp1] through [Exp4] to make settings for each TE-200,
TE-50, and TW-50 individually.
(2) Enter [0] in the [M-NET Address] field (unless otherwise specified).
(3) Select [SC/RC] to prohibit the operation from both the sub system controllers and the remote controllers.
Select [RC Only] to prohibit the operation only from the remote controllers.
WT09304X01
®
function. Do not use LAN2 for other functions.
®
function settings, refer to the Instruction Book (BACnet
69
®
function).

Advertisement